1.1.5 <strong>FP</strong>2<br />

1.1 Table of Relays, Memory Areas and Constants<br />

Item Numbering Function<br />

Relay External input (X) 2,048 points<br />

Turn on or off based on external input.<br />

relay<br />

(X0 to X127F)<br />

Memory<br />

area<br />

External<br />

output relay<br />

Internal relay<br />

(* Note 1)<br />

Link relay<br />

(* Note 1)<br />

(Y) 2,048 points<br />

(Y0 to Y127F)<br />

(R) 4,048 points<br />

(R0 to R252F)<br />

(L) 2,048 points<br />

(L0 to L127F)<br />

Externally outputs on or off state.<br />

Relay which turns on or off only within program.<br />

This relay is a shared relay used for<br />

MEWNET link system.<br />

Timer (T) 1,024 , points p<br />

If a TM instruction has timed out, , the con-<br />

(* Notes 1 and 2)<br />

(T0 to t T999/ C1000 to t C1023)<br />

ttactt with ith th the same number b turns t on.<br />

Counter (C) If a CT instruction has counted up, p, the con-<br />

(* Notes 1 and 2)<br />

ttactt with ith th the same number b turns t on.<br />

Pulse relay (P) 1,024 points<br />

This relay is used to turn on only for one<br />

(P0 to P63F)<br />

scan duration programmed with the OT"<br />

and OT# instructions.<br />

Special internal (R) 176 points<br />

Relay which turns on or off based on spe-<br />

relay<br />

(R9000 to R910F)<br />

cific conditions and is used as a flag.<br />

External input<br />

relay<br />

External<br />

output relay<br />

(WX) 128 words<br />

(WX0 to WX127)<br />

(WY) 128 words<br />

(WY0 to WY127)<br />

Internal relay (WR) 253 words<br />

(WR0 to WR252)<br />

Link relay (WL) 128 words<br />

(WL0 to WL127)<br />

Data register<br />

(* Note 1)<br />

Link data register<br />

(* Note 1)<br />

Timer/Counter<br />

set value area<br />

(* Note 1)<br />

Timer/Counter<br />

elapsed value area<br />

(* Note 1)<br />

File register<br />

(* Notes 1 and 3)<br />

Special data<br />

register<br />

(DT) 6,000 words<br />

(DT0 to DT5999)<br />

(LD) 256 words<br />

(LD0 to LD255)<br />

(SV) 1,024 words<br />

(SV0 to SV1023)<br />

(EV) 1,024 words<br />

(EV0 to EV1023)<br />

(FL) <strong>FP</strong>2 (16 K):<br />

0 to 14,333 words<br />

(FL0 to FL14332)<br />

<strong>FP</strong>2 (32 K)<br />

(when expanded):<br />

0 to 30,717 words<br />

(FL0 to FL30716)<br />

(DT) 256 words<br />

(DT90000 to DT90255)<br />

Code for specifying 16 external input points<br />

as one word (16 bits) of data.<br />

Code for specifying 16 external output<br />

points as one word (16 bits) of data.<br />

Code for specifying 16 internal relay points<br />

as one word (16 bits) of data.<br />

Code for specifying 16 link relay points as<br />

one word (16 bits) of data.<br />

Data memory used in program. Data is<br />

handled in 16-bit units (one word).<br />

This is a shared data memory which is<br />

used within the MEWNET link system.<br />

Data is handled in 16-bit units (one word).<br />

Data memory for storing a target value of a<br />

timer and an initial value of a counter.<br />

Stores by timer/counter number.<br />

Data memory for storing the elapsed value<br />

during operation of a timer/counter. Stores<br />

by timer/ counter number.<br />

Data memory used in program. Data is<br />

handled in 16-bit units (one word).<br />

Data memory for storing specific data.<br />

Various settings and error codes are<br />

stored.<br />

Index register (I) 14 words (I0 to ID) Register can be used as an address of<br />

memory area and constants modifier.<br />