1.1.3 <strong>FP</strong>Σ<br />

12k type<br />

Rel elay<br />

Memmory<br />

area (wo words)<br />

External input relay<br />

(see note 1)<br />

<strong>FP</strong>G−C32T/C32TTM<br />

External input relay<br />

(see note 1)<br />

<strong>FP</strong>G−C32T2/C32T2TM<br />

<strong>FP</strong>G−C24R2/C24R2TM<br />

<strong>FP</strong>G−C28P2<br />

External output relay<br />

(see note 1)<br />

<strong>FP</strong>G−C32T/C32TTM<br />

External output relay<br />

(see note 1)<br />

<strong>FP</strong>G−C32T2/C32T2TM<br />

<strong>FP</strong>G−C24R2/C24R2TM<br />

<strong>FP</strong>G−C28P2<br />

Internal relay<br />

(see note 2)<br />

Link relay<br />

(see note 2)<br />

Timer<br />

(see notes 2<br />

and 3)<br />

1.1 Table of Relays, Memory Areas and Constants<br />

Item Number<br />

of points<br />

Memory area available for use Function<br />

512 X0−X31F Turns on or off based on<br />

external input.<br />

Counter<br />

(see notes 2<br />

and 3)<br />

1184 X0−X73F<br />

512 Y0−Y31F Externally outputs on or off state.<br />

1184 Y0−Y73F<br />

1568 R0−R97F Turns on or off only within a<br />

program.<br />

1024 L0−L63F Shared relay used for <strong>PLC</strong> link.<br />

1024 T0−T1007/C1008−C1023 Goes on when the timer reaches<br />

the specified time.<br />

Corresponds to the timer<br />

number.<br />

1024 C1008−C1023/T0−T1007 Goes on when the counter<br />

increments.<br />

Corresponds to the counter<br />

number.<br />

Special internal relay 176 R9000−R910F Turns on or off based on specific<br />

conditions. Used as a flag.<br />

External input relay 32 words WX0−WX31 Code for specifying 16 external<br />

(see note 1)<br />

input points as one word (16<br />

<strong>FP</strong>G−C32T/C32TTM<br />

bits) ) of data.<br />

External input relay<br />

(see note 1)<br />

<strong>FP</strong>G−C32T2/C32T2TM<br />

<strong>FP</strong>G−C24R2/C24R2TM<br />

<strong>FP</strong>G−C28P2<br />

74 words WX0−WX73<br />

External output relay 32 words WY0−WY31 Code for specifying 16 external<br />

(see note 1)<br />

output points as one word (16<br />

<strong>FP</strong>G−C32T/C32TTM<br />

bits) ) of data.<br />

External output relay<br />

(see note 1)<br />

<strong>FP</strong>G−C32T2/C32T2TM<br />

<strong>FP</strong>G−C24R2/C24R2TM<br />

<strong>FP</strong>G−C28P2<br />

74 words WY0−WY73<br />

Internal relay<br />

(see note 2)<br />

98 words WR0−WR97 Code for specifying 16 internal<br />

relay points as one word (16<br />

bits) of data.<br />

Link relay 64 words WL0−WL63 Code for specifying 16 link relay<br />

points as one word (16 bits) of<br />

data.<br />

<strong>CTi</strong> <strong>Automation</strong> - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: info@ctiautomation.net<br />