No. Name<br />

Default<br />

value<br />

Descriptions<br />

410 Unit No. setting 1 1 to 99<br />

Communication<br />

mode setting<br />

Computer link<br />

Computer link<br />

General-purpose communications Note2)<br />

412<br />

Selection of modem<br />

connection<br />

Disabled Enabled/Disabled<br />

413 Communication<br />

format setting<br />

415<br />

420<br />

421<br />

Communication<br />

speed (Baud rate)<br />

setting<br />

Starting address for<br />

received buffer of<br />

general (serial data)<br />

communication mode<br />

Buffer capacity<br />

setting for data<br />

received of general<br />

(serial data)<br />

communication mode<br />

Data lenght<br />

bit: 8 bits<br />

Parity check:<br />

“with odd”<br />

Stop bit: 1 bit<br />

9600 bps<br />

4096 0 to 32764<br />

2048 0 to 2048<br />

410 Unit No. setting 1 1 to 99<br />

412<br />

Communication<br />

mode setting<br />

Selection of modem<br />

connection<br />

413 Communication<br />

format setting<br />

415<br />

416<br />

417<br />

Communication<br />

speed (Baud rate)<br />

setting<br />

Starting address for<br />

received buffer of<br />

general (serial data)<br />

communication mode<br />

Buffer capacity<br />

setting for data<br />

received of general<br />

(serial data)<br />

communication mode<br />

<strong>FP</strong>0R<br />

Enter the settings for the various items.<br />

- Data lenght bit: 7 bits/8 bits<br />

- Parity check: none/with odd/with even<br />

- Stop bit: 1 bit/2 bits<br />

- The following setting is valid only when<br />

the communication mode specified by<br />

system register 412 has been set to<br />

“General-purpose serial communication”.<br />

- Terminator CR/CR+LF/None<br />

- Header: STX not exist/STX exist<br />

2400 bps / 4800 bps / 9600 bps /<br />

19200 bps / 38400 bps / 57600 bps /<br />

115200 bps<br />

Computer link<br />

General-purpose serial communication<br />

Computer link<br />

PC(<strong>PLC</strong>) link<br />

MODBUS RTU<br />

Disabled Enabled/Disabled<br />

Data lenght<br />

bit: 8 bits<br />

Parity check:<br />

Odd<br />

Stop bit: 1 bit<br />

9600 bps<br />

0 0 to 32764<br />

2048 0 to 2048<br />

Enter the settings for the various items.<br />

- Data lenght bit: 7 bits/8 bits<br />

- Parity check: none/with odd/with even<br />

- Stop bit: 1 bit/2 bits<br />

- The following setting is valid only when<br />

the communication mode specified by<br />

system register 412 has been set to<br />

“General-purpose serial communication”.<br />

- Terminator CR/CR+LF/None/ETX<br />

- Header: STX not exist/STX exist<br />

2400 bps / 4800 bps / 9600 bps /<br />

19200 bps / 38400 bps / 57600 bps /<br />

115200 bps<br />

Note1) The communication format in a <strong>PLC</strong> link is fixed at the following settings:<br />

Data length is 8 bits, odd parity, stop bit is 1.<br />

The communication speed (baud rate) is fixed at 115200 bps.<br />

Note2) The general-purpose communication with the tool port is available only in RUN mode. In PROG<br />

mode, the computer link mode must be used regardless of settings.<br />