Laying instructions for ductile cast iron<br />

pressure pipes, fittings and valves, equipped<br />

with thrust-resisting joint Novo SIT<br />

2286 ®<br />

General instructions<br />

For laying pressure pipes, fittings and valves with thrust resisting joint Novo SIT ® “laying<br />

instructions for ductile cast iron pressure pipes and fittings with TYTON ® -joint” should be observed.<br />

Application field<br />

Novo SIT ® -locking rings are available for dimensions DN 80 up to DN 1000 and for nominal<br />

pressures up to<br />

DN 80 — 300 25 bar (on request up to 40 bar)<br />

DN 350 — 600 16 bar (on request up to 25 bar)<br />

DN 700 — 800 10 bar (on request up to 16 bar)<br />

This self-anchoring, thrust resisting socket joint substitutes concrete anchoring blocks.<br />

The suitable number of thrust resisting connections has been laid down in DVGW standard GW 368<br />

and has to be observed.<br />

Before installation in lines for bridges, ducts or river-crossings, please contact our service team.<br />

Figure:<br />

Novo SIT ® -ring with vulcanised<br />

segments made of chromium steel.<br />

Assembling steps<br />

TYTON ® -ring Novo SIT ® -ring<br />