Compressed <strong>air</strong> line systems - Ø 15-28 mm<br />

Assembly instructions for plastic tube lines<br />

In order to guarantee a safe and this way perfect installation,<br />

please note the following points:<br />

· The pipe clamps need to be mounted in a way that the pipe has<br />

enough clearance to shift it to and fro<br />

· There must be no burr at the ends of the tubes in order to avoid<br />

damages at the O-rings of the connector<br />

· Provide the tubes with a chamfer in order to facilitate the assembly<br />

· Cut the tubes with pipe shears RS 28 (Item No 215 1528) in order to<br />

achieve an optimum separation (90°)<br />

· In order to avoid loss of pressure in the system, make sure to plug the<br />

tubes always up to the limit stop into the connector<br />

(also see marking on the connector)<br />

· For the installation of the <strong>compressed</strong> <strong>air</strong> piping system around a pillar,<br />

please observe the longitudinal extension of the tubes and connectors<br />

(recommended distance from the wall about 30 mm)<br />

Correction factors length extension<br />

Correction factors for the length extension of plastic tubes:<br />

Tube (smooth) Factor 1.5<br />

Tube (middle) Factor 1.3<br />

Tube (hard) Factor 1.0<br />

Exemplary calculation:<br />

The <strong>compressed</strong> <strong>air</strong> pipe (hard tube) with a length of 150 m which is laid in<br />

a hall where the environmental temperature is between +15 to +40°C<br />

( T is 25°C) will extend by: l = 1.0 x 10 -4 /°C x 150 x 25°C<br />

l = 0.375 m<br />

Easily extending an<br />

existing tube system<br />

The plug connectors and tubes can be used to<br />

install a self-contained system<br />

or extend or modify an existing tube system<br />

(refer to the right).<br />

Description of the water separator system<br />

1. 2.<br />

water separator for 28 mm<br />

<strong>compressed</strong> <strong>air</strong> line systems<br />

You can construct a water separator<br />

for 28 mm <strong>compressed</strong> <strong>air</strong> line<br />

systems with a standard T-piece, item<br />

No. 215 2828 and the brass insert,<br />

item No. 215 2829.<br />

1. Insert the short part of the insert, item No 215 2829<br />

into the plastic tube or into the copper tube.<br />

2. Plug the tube with the insert up to the limit stop into the T-piece.<br />

By a 1/4 turn of the screw cap, the holding system is double<br />

protected. This way, the penetration of water into the stub is<br />

prevented.<br />

· For the installation of several vertical tubes we recommend to mount<br />

first the pipe clamps of the horizontal piping which put the system under<br />

pressure and in the second step the vertical clamps and connectors.<br />

This way you can avoid that the vertical tubes are oblique after the<br />

installation.<br />

· If there is no refrigeration dryer in the installation of the <strong>compressed</strong><br />

<strong>air</strong> piping system, it is recommended to use our T-connectors with<br />

integrated water separator (Item No. 215 2222). This way the condensed<br />

water can be collected at a certain point.<br />

· For the installation of the <strong>compressed</strong> <strong>air</strong> piping system a correct heat<br />

extension calculation needs to be performed first in order to avoid the<br />

bending of tubes and connections.<br />

The specific coefficient for the length extension (lK) for polyamide =<br />

10 -4 /C° corresponds to 0.1 mm/°C.<br />

The formula to calculate the length extension:<br />

l = factor x lK (10 -4 /C°) x length of the tube (l) x temperature ( T)<br />

Using a straight screw-in connector<br />

Using a screw coupling<br />

Using a screw-in connecting piece<br />

Wet <strong>air</strong><br />

Water<br />

separator<br />

Dry<br />

<strong>air</strong><br />

By the water separator-<br />

T-connector the so-called "goose<br />

necks“ do not apply since, because<br />

of the fully developed technique, a<br />

penetration of water to the branch<br />

lines is prevented.<br />

When installing this connector,<br />

make sure that a horizontal tying<br />

of the connector is guaranteed. The<br />

connector is marked accordingly, so<br />

that a wrong assembly is prevented.<br />

118 Built according to CE directives