d. The electricity used by fossil-fuelled equipment and its ancillaries, including<br />

fans in unit heaters and gas boosters, is included in the auxiliary energy.<br />

e. For the purposes of heating, cooling, and auxiliary energy calculations, the<br />

ventilation should operate on a flat profile that is on during the occupied period<br />

only, with a flow rate determined by the product of the peak occupancy density<br />

and fresh air rate per person (both from the <strong>NCM</strong> Activity Database). The<br />

profile is the same for both natural and mechanical ventilation and does not<br />

modulate with the occupancy profile.<br />

Table 4: HVAC Seasonal system efficiencies in the notional building<br />

Servicing strategy SCoP † Cooling<br />

SSEER<br />

Auxiliary energy<br />

Heating with natural<br />

ventilation<br />

0.73 N/A See paragraph 45.a<br />

Heated with mechanical<br />

ventilation<br />

0.78 N/A See paragraph 45.b<br />

Fully air-conditioned 0.83 1.67 See paragraph 45.c<br />

Changeover mixed-mode<br />

with natural ventilation<br />

0.73 2.25 †† See paragraph 45.a<br />

Changeover mixed-mode<br />

with mechanical ventilation<br />

0.78 2.25 †† See paragraph 45.b<br />

No heating with natural<br />

ventilation<br />

N/A N/A 0<br />

†<br />

Referred to as Seasonal System Efficiency (SSEff) in iSBEM User guide.<br />

††<br />

This SSEER includes an allowance for fan energy when the system operates, so no<br />

additional auxiliary energy needs to be determined beyond what is described above.<br />

45. The auxiliary energy per unit floor area in the notional building must be calculated<br />

as follows:<br />

a. For heated only and naturally ventilated spaces: the product of 0.61 W/m 2 and<br />

the annual hours of operation of the heating system from the <strong>NCM</strong> Activity<br />

Database.<br />

b. For mechanically ventilated spaces: the product of the outside air rate for the<br />

space, the annual hours of operation (both from the Activity Database) and the<br />

appropriate specific fan power from Table 5. If the zone is heated, then the<br />

auxiliary energy should also include the energy from paragraph 45.a.<br />

c. For air-conditioned spaces: the product of the annual hours of operation and<br />

the greater of either:<br />

i. The product of the fresh air rate (from the <strong>NCM</strong> Activity Database) and the<br />

appropriate SFP from Table 5, or<br />

ii. 8.5 W/m 2 .<br />

17