c. If the total area of these elements is less than the appropriate allowance from<br />

clause 6.1.4 of Section 6, the balance must be made up of windows or<br />

rooflights as appropriate.<br />

d. If the total area of the copied elements exceeds the allowance from clause<br />

6.1.4 of Section 6, the copied areas must be retained, but no further area of<br />

windows or rooflights added. As noted in paragraph 28, smoke vents and other<br />

ventilation openings must be ignored in both the notional and actual buildings.<br />

e. The areas shown in clause 6.1.4 of Section 6, represent the areas of openings<br />

in the wall or roof and comprise the area of the glass plus the frame. The<br />

windows must have a frame factor of 0.1 (i.e. 90% of the area of the opening is<br />

glazed) and rooflights a frame factor of 0.3 (display windows have a frame<br />

factor of 0.1).<br />

36. In addition, the following rules apply:<br />

a. In the notional building, pedestrian and vehicle access doors must be taken as<br />

being opaque, i.e. with no glazing.<br />

b. No glazed area should be included in basements. In semi-basements, i.e.<br />

where the wall of the basement space is partly above ground, the percentages<br />

in clause 6.1.4 of Section 6 must include the above-ground part, with no<br />

glazing allowance for the below-ground part.<br />

HVAC 12 System Definition<br />

37. Each space in the notional building will have the same level of servicing as the<br />

equivalent space in the actual building. In this context, “level of servicing” means<br />

the broad category of environmental control, i.e.<br />

a. Unconditioned (i.e. neither heated nor mechanically cooled)<br />

b. Heated only with natural ventilation<br />

c. Heated only with mechanical ventilation<br />

d. Air-conditioned (i.e. heated and mechanically cooled)<br />

e. Mixed-mode cooling, where cooling operates only in peak season to prevent<br />

space temperatures exceeding a threshold temperature higher than that<br />

normally provided by an air-conditioning system. This can be accompanied by<br />

either natural or mechanical ventilation.<br />

38. A space is only considered as having air-conditioning if the system serving that<br />

space includes refrigeration. Night cooling using mechanical ventilation is not airconditioning.<br />

If the same mechanical ventilation system that is used for night<br />

cooling is also used to provide normal ventilation, then the space should be<br />

12 Heating Ventilation and Air Conditioning.<br />