Part One / Certification 1<br />

1.1 ASSESSMENT<br />

In the opinion <strong>of</strong> the Irish Agrément Board (IAB), the<br />

CPT Zons® AQUAstar® Wastewater Treatment System<br />

is satisfactory for the purpose defined above, and can<br />

meet the requirements <strong>of</strong> the Building Regulations 1997<br />

to 2007, as indicated in Section 1.2 <strong>of</strong> this Certificate.<br />

1.2 BUILDING REGULATIONS 1997 to 2007<br />

REQUIREMENT<br />

PART D – MATERIALS AND WORKMANSHIP<br />

D1 - The CPT Zons® AQUAstar® Wastewater<br />

Treatment System, used in accordance with this Irish<br />

Agrément Board Certificate, can meet the requirements<br />

for materials and workmanship.<br />

D3 - The CPT Zons® AQUAstar® Wastewater<br />

Treatment System, as certified in this Irish Agrément<br />

Board Certificate, is manufactured from proper materials<br />

and is fit for its intended use. See Part 4 <strong>of</strong> this<br />

Certificate.<br />

PART H - DRAINAGE AND WASTE DISPOSAL<br />

H1 Drainage systems<br />

The CPT Zons® AQUAstar® Wastewater Treatment<br />

System when installed, operated and maintained in<br />

Certificate No. 08/0318 / CPT Zons® AQUAstar®<br />

accordance with this Certificate, can meet Building<br />

Regulation requirements.<br />

H2 Septic tanks<br />

The CPT Zons® AQUAstar® Wastewater Treatment<br />

System is a mechanical aeration wastewater treatment<br />

system, for the treatment <strong>of</strong> domestic wastewater, when<br />

designed, installed and used in accordance with the EPA<br />

Wastewater treatment manual – Treatment Systems for<br />

Single Houses 2000.<br />

The quality <strong>of</strong> effluent from the CPT Zons® AQUAstar®<br />

Wastewater Treatment System can meet the Building<br />

Regulation requirements.<br />

Information on the design capacity, ventilation,<br />

safety and location requirements is given in this<br />

Irish Agrément Certificate. See Part 3 and 4 <strong>of</strong> this<br />

certificate.<br />

Part Two / Technical Specification and Control Data 2<br />

2.1 PRODUCT DESCRIPTION<br />

2.1.1 System Details<br />

The CPT Zons® AQUAstar® Wastewater Treatment<br />

System is a Sequential Batch Reactor (SBR),<br />

mechanical aeration wastewater treatment system for<br />

treatment <strong>of</strong> domestic wastewater, from dwellings with a<br />

population equivalent <strong>of</strong> up to ten persons.<br />

The CPT Zons® AQUAstar® Wastewater Treatment<br />

System settings are configured prior to installation, and<br />

subsequently adjusted at first service, to suit the actual<br />

hydraulic and biological loading on the system. These<br />

loadings must remain within the maximum loadings<br />

specified for the unit.<br />

The system elements and specifications are given in<br />

Table 1 and Figures 1 and 2.<br />

The treatment design criteria are given in Table 2.<br />

The tank is sub-divided into three chambers i.e. two<br />

interconnected primary settlement chambers and the<br />

third and final activation chamber. The CPT Zons®<br />

AQUAstar® kit, located in the activation chamber, is<br />

electronically controlled by the MULTICOM® 100 control<br />

unit/alarm. The control unit is fitted in an insulated box,<br />

on the riser wall, above the activation chamber.<br />

The system should be connected to the domestic power<br />

supply via the IP 66 rated junction box provided. It is<br />

<strong>For</strong> <strong>inspection</strong> <strong>purposes</strong> <strong>only</strong>.<br />

<strong>Consent</strong> <strong>of</strong> <strong>copyright</strong> <strong>owner</strong> <strong>required</strong> for any other use.<br />

connected to the dwelling served, through a residual<br />

current circuit breaker.<br />

100 mm diameter inlet and 32 mm diameter (1 1/4 “)<br />

outlet pipe connections are provided and provision is<br />

made for ventilation.<br />

All chambers are accessed via pedestrian duty<br />

reinforced concrete access covers, which are designed<br />

to be flush with ground level. The CPT Zons®<br />

AQUAstar® unit can be readily removed from the<br />

activation chamber for servicing or maintenance.<br />

Discharge from the tank is by pumped discharge.<br />

2.1.2 Treatment process<br />

The CPT Zons® AQUAstar® Wastewater Treatment<br />

System uses activated sludge/sequencing batch reactor<br />

technology to biologically treat domestic wastewater.<br />

The treatment process steps are as follows:<br />

1 Pre-treatment: Domestic wastewater flows by gravity,<br />

into the primary chambers, which provide for the<br />

settlement and storage <strong>of</strong> primary and surplus sludge,<br />

act as a buffer for the inflow and provide additional<br />

storage capacity if <strong>required</strong>.<br />

2 Treatment: When the wastewater in the primary tank<br />

reaches the <strong>required</strong> level, a fixed volume is siphoned<br />

EPA Export 24-08-2012:23:55:55