Application Manual – Liquid Cooled Generator Sets<br />

Load Running Requirements (Individual Load Steady–State Running)<br />

• Running kVA (RkVA) – the running kilovolt–amperes load.<br />

• Running kW (RkW) – the running kilowatt load.<br />

• Alternator kW (AkW) – the alternator capacity provided to compensate (to oversize)<br />

for non–linear distortion.<br />

• Running PF (RPF) – the steady–state running power factor of the load.<br />

• Efficiency – the ratio of output power to input power.<br />

• Running Amps (RAmps) – the running amperes for a load or step.<br />

Load Starting Requirements (Individual Load Starting)<br />

• Starting kW (SkW) – starting kilowatts of a load.<br />

• Starting kVA (SkVA)– starting kilovolt–amperes of a load.<br />

• Starting PF (SPF) – starting power factor is the power factor of the load at the time it<br />

is initially energized or started.<br />

Transient Step Load Requirements (Combined Load in Each Step Load Application)<br />

• Maximum Step kW – the maximum step load in kW (sum of individual load starting<br />

kilowatts (SkW)) in the step.<br />

• Maximum Step kVA – the maximum step load in kVA (sum of individual load starting<br />

kilovolt–amperes (SkVA)) in the step.<br />

• Cumulative Step kW – the Maximum Step kW added to the running kW of the previous<br />

step(s).<br />

• Cumulative Step kVA – the Maximum Step kVA added to the running kVA of the previous<br />

step(s).<br />

• Effective Step kW – the Cumulative Step kW times a multiplier to account for the<br />

reduced load effect due to sustained reduced output voltage during the transient step<br />

load.<br />

• Effective Step kVA – the Cumulative Step kVA times a multiplier to account for the<br />

reduced load effect due to sustained reduced output voltage during the transient step<br />

load.<br />

Transient Surge Load Requirements (Combined Load for all Loads that Require<br />

Random Peak Operating Power)<br />

• Peak kW (PkW) – the sudden increase of power in kW demanded by a cyclical load<br />

as it starts, or by other surge loads like welders and medical imaging equipment<br />

when they operate.<br />

• Peak kVA (PkVA) the sudden increase of power in kVA demanded by a cyclical load<br />

as it starts, or by other surge loads like welders and medical imaging equipment<br />

when they operate.<br />

• Cumulative Surge kVA – the Peak kVA added to the running kVA of all other non–<br />

surge loads.<br />

• Cumulative Surge kW – the Peak kW added to the running kW of all other non–surge<br />

loads.<br />

A–8 APPENDIX A<br />

Rev. Jan 2011