Application Manual – Liquid Cooled Generator Sets<br />
Load Running Requirements (Individual Load Steady–State Running)<br />
• Running kVA (RkVA) – the running kilovolt–amperes load.<br />
• Running kW (RkW) – the running kilowatt load.<br />
• Alternator kW (AkW) – the alternator capacity provided to compensate (to oversize)<br />
for non–linear distortion.<br />
• Running PF (RPF) – the steady–state running power factor of the load.<br />
• Efficiency – the ratio of output power to input power.<br />
• Running Amps (RAmps) – the running amperes for a load or step.<br />
Load Starting Requirements (Individual Load Starting)<br />
• Starting kW (SkW) – starting kilowatts of a load.<br />
• Starting kVA (SkVA)– starting kilovolt–amperes of a load.<br />
• Starting PF (SPF) – starting power factor is the power factor of the load at the time it<br />
is initially energized or started.<br />
Transient Step Load Requirements (Combined Load in Each Step Load Application)<br />
• Maximum Step kW – the maximum step load in kW (sum of individual load starting<br />
kilowatts (SkW)) in the step.<br />
• Maximum Step kVA – the maximum step load in kVA (sum of individual load starting<br />
kilovolt–amperes (SkVA)) in the step.<br />
• Cumulative Step kW – the Maximum Step kW added to the running kW of the previous<br />
step(s).<br />
• Cumulative Step kVA – the Maximum Step kVA added to the running kVA of the previous<br />
step(s).<br />
• Effective Step kW – the Cumulative Step kW times a multiplier to account for the<br />
reduced load effect due to sustained reduced output voltage during the transient step<br />
load.<br />
• Effective Step kVA – the Cumulative Step kVA times a multiplier to account for the<br />
reduced load effect due to sustained reduced output voltage during the transient step<br />
load.<br />
Transient Surge Load Requirements (Combined Load for all Loads that Require<br />
Random Peak Operating Power)<br />
• Peak kW (PkW) – the sudden increase of power in kW demanded by a cyclical load<br />
as it starts, or by other surge loads like welders and medical imaging equipment<br />
when they operate.<br />
• Peak kVA (PkVA) the sudden increase of power in kVA demanded by a cyclical load<br />
as it starts, or by other surge loads like welders and medical imaging equipment<br />
when they operate.<br />
• Cumulative Surge kVA – the Peak kVA added to the running kVA of all other non–<br />
surge loads.<br />
• Cumulative Surge kW – the Peak kW added to the running kW of all other non–surge<br />
loads.<br />
A–8 APPENDIX A<br />