24.01.2013 Views

appendix

appendix

appendix

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

Entering Loads<br />

Definition of Terms<br />

APPENDIX A<br />

Rev. Jan 2011<br />

Application Manual – Liquid Cooled Generator Sets<br />

A minimum of 10 percent overload capability is available for prime power ratings per<br />

engine rating standards BS 5514 and DIN 6271. Not every generator set configuration is<br />

available for prime duty.<br />

When generator sets are paralleled with a utility service for an extended period of time,<br />

they should not be operated in excess of their base load rating. Generally the base load<br />

rating of a generator set is significantly lower than its prime power rating. Base load<br />

ratings for generator sets are available from the factory or your local Cummins Power<br />

Generation distributor.<br />

Voltage<br />

Available voltage choices are a function of selected frequency. Default values are<br />

277/480, Series Wye.<br />

The next and most important step in sizing a generator set is identifying every type and<br />

size of load the generator set will power. As with most operations in GenSize, the loads<br />

can be entered either from the menu under Projects, Add New Load, or from the icons<br />

located on the tool bar. After selecting a load type, the load entry form will appear. Each<br />

load form will open with load characteristic defaults which can all be changed. Enter all of<br />

the required information. If you are unsure what any of the items are, check the online<br />

Help for an explanation. As each load is entered, they will appear in a list on the left side<br />

of the screen under the project you are working on. Selecting (with a mouse click) one of<br />

the loads in the list will display the load operating characteristics on the right of the<br />

screen. Double clicking a load icon will open the load entry form for that load and you<br />

can edit the load from here. The following is intended to help you understand load<br />

parameters and the way they are calculated by GenSize.<br />

Identify all of the different type and size loads the generator set will need to support. If<br />

you have more than one load of a given size and type, you only need to enter it once,<br />

unless you want each of the loads to carry a different description. The quantity of each<br />

load can be set when you enter the load in the step starting sequence. As described later<br />

in this section<br />

Cummins Power Generation has researched the starting and running characteristics of<br />

many of the common loads and have included defaults for these load characteristics in<br />

GenSize. You can choose to use the defaults or, if you know the characteristics of your<br />

load are different, change the load characteristic. If you have a load type other than what<br />

is identified in GenSize, use a miscellaneous load to define the load starting and running<br />

requirements.<br />

Based on the load characteristics, GenSize calculates values for running kW (RkW),<br />

running kVA (RkVA), starting kVA (SkVA), starting kW (SkW), starting power factor (SPF),<br />

peak kVA (PkVA), peak kW (PkW), and running amps (RAmps). When non–linear loads<br />

are present, it may be necessary to over–size the alternator, and GenSize calculates a<br />

value for the alternator kW (AkW) for the load.<br />

Note that when entering single–phase loads on a three–phase generator set, GenSize<br />

assumes that all three phase loads will be balanced among the three phases. Therefore,<br />

the single–phase loads are converted to an equivalent three–phase load for sizing<br />

purposes. This results in the single–phase load current being distributed across the three<br />

phases so the single–phase load current is divided by 1.73. When a single phase load is<br />

entered for a three phase set application, the actual single phase current will be displayed<br />

in the load entry form, but when the load is entered into a step (the step load is the<br />

balanced load applied to the generator), the step load current is converted to the<br />

equivalent three phase current.<br />

The following abbreviations are used in GenSize for calculating individual load running<br />

and starting requirements, step load requirements, and transient surge load<br />

requirements. These abbreviations are used on load forms and reports in the application<br />

and in the following discussion intended to document some of the calculations performed<br />

in GenSize.<br />

A–7

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!