appendix
appendix appendix
LINE Application Manual – Liquid Cooled Generator Sets MOTOR STARTING DIAGRAM 3 2 1 START: CLOSE 1–2–3 RUN: CLOSE 4–5–6 Wound Rotor Motor Starting LINE 4 6 5 4 MOTOR MOTOR STARTING DIAGRAM 5 3 2 1 6 7 RESISTORS Synchronous Motor Starting General Application Note 8 9 kVA & TORQUE (% F. L.) B–6 APPENDIX B Rev. Jan 2011 600 500 400 300 200 100 TYPICAL TORQUE AND KVA CURVES FOR SQUIRREL CAGE INDUCTION MOTORS TORQUE KVA 20 40 60 80 100 SPEED (% SYNCHRONOUS) Starting: A wound rotor motor can have the same starting torque as a squirrel cage motor but with less current. It differs from squirrel cage motors only in the rotor. A squirrel cage motor has short circuit bars, whereas a wound rotor motor has windings, usually three–phase. Application Notes: Starting current, torque, and speed characteristics can be changed by connecting the proper amount of external resistance into the rotor. Usually, wound rotor motors are adjusted so that the starting kVA is about 1.5 times running kVA. This is the easiest type of motor for a generator set to start. MOTOR ROTOR kVA & TORQUE (% F. L.) 600 500 400 300 200 TYPICAL TORQUE AND KVA CURVES FOR WOUND ROTOR MOTORS 100 START: CLOSE 1–2–3 TORQUE STEP #1: CLOSE 4–5 STEP #2: cLOSE 6–7 20 40 60 80 100 RUN: CLOSE 4–5–6 SPEED (% SYNCHRONOUS) Starting: Synchronous motors can use most of the starting methods discussed. Synchronous motors rated 20 HP and greater have starting characteristics similar to wound rotor motors. Application Notes: Synchronous motors are in a class by themselves. There are no standards for performance, frame size, or connections. Motors rated 30 HP or less have high locked rotor currents. They can be used in applications where power factor correction is desired. (Use the standard code letter when the actual letter is not known.) If the reduced voltage motor starter has a time or rate adjustment, adjust the settings to obtain about two seconds between taps. This allows time for the motor to approach rated speed and thus reduce the peak kVA at the time of switching, as shown below. Note that at the minimum setting there is not much improvement over full voltage starting. In some applications the inrush current is so low that the motor shaft will not start to turn on the first tap, nor even the second. For those applications there is little reduction of starting kVA from the standpoint of the generator set. KVA
APPENDIX B FULL–VOLTAGE KVA CURVE kVA (% F. L.) 600 500 400 300 200 100 KVA PEAK AT MINIMUM TIME OR RATE SETTING OF STARTER 20 40 60 80 100 SPEED (% SYNCHRONOUS) Rev. Jan 2011 Application Manual – Liquid Cooled Generator Sets KVA PEAK AT MAXIMUM TIME OR RATE SETTING OF STARTER B–7
- Page 1 and 2: Chapter 8 Appendices
- Page 3 and 4: Application Manual - Liquid Cooled
- Page 5 and 6: Application Manual - Liquid Cooled
- Page 7 and 8: Application Manual - Liquid Cooled
- Page 9 and 10: Application Manual - Liquid Cooled
- Page 11 and 12: Application Manual - Liquid Cooled
- Page 13 and 14: Application Manual - Liquid Cooled
- Page 15 and 16: Application Manual - Liquid Cooled
- Page 17 and 18: Application Manual - Liquid Cooled
- Page 19 and 20: Application Manual - Liquid Cooled
- Page 21 and 22: Application Manual - Liquid Cooled
- Page 23 and 24: APPENDIX B CONTENTS APPENDIX B CONT
- Page 25 and 26: LINE APPENDIX B 3 2 1 Autotransform
- Page 27: LINE 3 2 1 APPENDIX B MOTOR STARTIN
- Page 31 and 32: Application Manual - Liquid Cooled
- Page 33 and 34: Application Manual - Liquid Cooled
- Page 35 and 36: Application Manual - Liquid Cooled
- Page 37 and 38: Application Manual - Liquid Cooled
- Page 39 and 40: Application Manual - Liquid Cooled
- Page 41 and 42: Application Manual - Liquid Cooled
- Page 43 and 44: Application Manual - Liquid Cooled
- Page 45 and 46: Application Manual - Liquid Cooled
- Page 47 and 48: Application Manual - Liquid Cooled
- Page 49 and 50: Application Manual - Liquid Cooled
- Page 51 and 52: Application Manual - Liquid Cooled
- Page 53 and 54: Application Manual - Liquid Cooled
- Page 55 and 56: Application Manual -- Liquid Cooled
- Page 57 and 58: Application Manual -- Liquid Cooled
- Page 59: Application Manual -- Liquid Cooled
APPENDIX B<br />
FULL–VOLTAGE<br />
KVA CURVE<br />
kVA (% F. L.)<br />
600<br />
500<br />
400<br />
300<br />
200<br />
100<br />
KVA PEAK AT MINIMUM<br />
TIME OR RATE SETTING<br />
OF STARTER<br />
20 40 60 80 100<br />
SPEED (% SYNCHRONOUS)<br />
Rev. Jan 2011<br />
Application Manual – Liquid Cooled Generator Sets<br />
KVA PEAK AT MAXIMUM<br />
TIME OR RATE SETTING<br />
OF STARTER<br />
B–7