24.01.2013 Views

appendix

appendix

appendix

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

Application Manual – Liquid Cooled Generator Sets<br />

• The surge kVA exceeds generator set capacity. The surge kVA requirement is similar<br />

to the surge kW requirement except that there is no derating for altitude or ambient<br />

temperature. GenSize uses the greater of cumulative kVA and Peak kVA (if any) to<br />

determine the load surge kVA requirement.<br />

• The alternator kW required exceeds the alternator capacity, which may be derated for<br />

altitude and ambient temperature by the project parameters. The altitude knee for<br />

alternators, however, is 1000m (3280 ft) and the temperature knee 40° C (104° F).<br />

Alternator kW will be derated 3% per 500m (1640 ft) of altitude above the knee and<br />

3% per 5° C (9° F) of ambient temperature over the knee.<br />

• The alternator kVA required exceeds alternator capacity, which can be derated by<br />

altitude and temperature in the same way as the alternator kW.<br />

• The total non–linear load requirement exceeds 25 percent of the total load requirement.<br />

This will exclude shunt–excited generators where PMG excitation is not available.<br />

The total non–linear load requirement is the sum of the Alternator kW values of<br />

all of the non–linear loads.<br />

• The calculated voltage and frequency dips exceed the limits set in the current project<br />

parameters.<br />

• Starting voltage dip is calculated using the higher of two values: dip based on the<br />

maximum Step kW or on the maximum step kVA.<br />

• Peak voltage dip is calculated only if loads in the project exhibit a running surge<br />

(cyclic loads or loads like medical imaging that have a high peak power requirement<br />

when they are operated.<br />

• Frequency dip is calculated using the higher of two values: maximum Step kW or<br />

Peak kW from loads which exhibit running surge.<br />

• The message, “No generator set is available that meets your running load requirements”<br />

usually means that something in the New Project Parameters has been<br />

changed after having specified the running load. For instance, you will get the message<br />

if you change from diesel to natural gas fuel or from no sound attenuation to<br />

Quite Site and the running load you had specified exceeds the capacity of the largest<br />

natural gas or Quite Site generator set available. It may also mean that your project<br />

falls into a “gap” in the Cummins Power Generation product line. At this point, lowering<br />

the minimum percent rated load in the project parameters could allow a recommended<br />

set. If this is the case, contact your local Cummins Power Generation distributor<br />

for help.<br />

• The message, “No generator set is available which meets your frequency or voltage<br />

dip requirements” generally means that the surge requirement of some load step is<br />

forcing selection of such a large generator set that the steady state running load falls<br />

below 30 percent of the generator set capacity. Since Cummins Power Generation<br />

does not recommend running at less than 30 percent of rated capacity, no set can be<br />

recommended. At this point, you may have several choices:<br />

• Increase the allowable voltage or frequency dip.<br />

• Reduce the minimum percent rated load to less than 30 percent.<br />

• Apply loads in more steps to lower the individual step surge load.<br />

• Provide reduced–voltage motor starting.<br />

• Parallel generator sets.<br />

• Add loads that do not have a high starting surge (lights, resistive loads, etc.).<br />

A–20 APPENDIX A<br />

Rev. Jan 2011

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!