24.01.2013 Views

appendix

appendix

appendix

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

APPENDIX A<br />

Application Manual – Liquid Cooled Generator Sets<br />

Site Rated Max SkW and Max SkVA<br />

Displays the site–rated (derated when necessary for altitude and ambient temperature)<br />

maximum SkW and SkVA the generator set configuration can accommodate. If the<br />

display is red, the generator set cannot recover to a minimum of 90 percent of rated<br />

voltage with required Step or Peak load. One of the sizing philosophies for surge loading<br />

is that, with the surge load applied, the generator set must be able to recover to 90<br />

percent of rated voltage so that motors can develop adequate accelerating torque. If the<br />

generator set recovers to 90 percent of rated voltage, a motor will develop 81 percent of<br />

rated torque, which has been shown by experience to provide acceptable motor starting<br />

performance.<br />

If the display is yellow, the generator set can recover to a minimum of 90 percent of rated<br />

voltage with required surge load, but only because the surge requirement has been<br />

reduced. GenSize will reduce the surge requirement in recognition of the fact that the<br />

generator set output voltage is reduced while loads having starting power requirements<br />

approaching the maximum generator set capacity are starting.<br />

Temperature Rise At Full Load<br />

Displays the temperature rise the alternator will not exceed while supplying load up to<br />

and including the generator set full–load rating. Each individual generator set model will<br />

have one or more of the following temperature rise alternators available which may be<br />

specified in the current project parameters: 80° C, 105°C, 125° C and 150° C. Of course,<br />

the actual temperature rise of an alternator is a function of actual connected load.<br />

Therefore, GenSize may recommend a generator set with a lower or higher temperature<br />

rise option than specified in the New Project Parameters since the set recommendation is<br />

based on connected load. Connected load may be less than the full generator set<br />

capacity or, in the case of non–linear loads, the alternator may be required to be rated at<br />

greater than the set capacity. In any case, the set recommendation will limit the<br />

alternator temperature rise to that specified in the New Project Parameters.<br />

Excitation<br />

Displays the type of excitation system to be supplied with a generator set. If the display<br />

is red, the generator set is shunt excited and the percentage of non–linear load exceeds<br />

25 percent of the load running requirement, RkW. The PMG excitation system is<br />

recommended for applications that have a high–linear load content. Unless the PMG<br />

option is unavailable, Cummins Power Generation does not recommend using shunt<br />

excited generator sets if the non–linear load requirement is more than 25 percent of the<br />

total load requirement.<br />

The non–linear load requirement is calculated by adding the Running kW from all of the<br />

loads where Alternator kW exceeds Running kW. This will be the case for UPS loads,<br />

variable frequency motors, and solid state motor starters which are not equipped with an<br />

automatic bypass. This Alternator kW sum is then divided by the sum of the Running kW<br />

from all of the loads.<br />

Why a generator set may not be recommended: Several factors can cause a generator<br />

set to not be recommended.<br />

• Running kW requirement may exceed the rating of the generator set. Project parameters<br />

such as altitude, ambient temperature and prime power duty may cause the<br />

generator set to be derated and fall below project requirements.<br />

• The Running kW may be below the minimum of 10 to 30 percent of rated generator<br />

set capacity, as specified in the current project parameters (30 percent is default, as<br />

recommended by Cummins Power Generation).<br />

• The surge kW requirement may exceed generator capacity, which may have fallen<br />

below project requirements because of derating for altitude and ambient temperature.<br />

GenSize uses the greater Cumulative kW and Peak kW to determine the load surge<br />

kW.<br />

Rev. Jan 2011<br />

A–19

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!