Miscellaneous<br />
Load Calculations<br />
APPENDIX A<br />
Rev. Jan 2011<br />
Application Manual – Liquid Cooled Generator Sets<br />
occur. This occurs when rapidly changing UPS input frequency results from a sudden<br />
transient load change on a generator set. During this transient event, static UPSs with<br />
solid–state bypass switches must break synch with the source and disable the bypass.<br />
RkW RkW = RkVA x RPF<br />
RkVA RkVA = (Output kVA x Recharge Rate) ÷ Efficiency<br />
RPF Running power factor as entered or default<br />
SkW SkW = RkW<br />
SkVA SkVA = RkVA<br />
SPF SPF = RPF<br />
AkW For 3 pulse, AkW = 2.5 x RkW<br />
For 6 pulse, AkW = 1.4 x RkW<br />
For 12 pulse, AkW = 1.1.5 x RkW<br />
With input filter, AkW = 1.15 x RkW for 6 and 12 pulse<br />
AkW = 1.40 x RkW for 3 pulse<br />
Ramps 1∅ Ramps = (RkVA x 1000) ÷ voltage<br />
3∅ Ramps = (RkVA x 1000) ÷ (voltage x 1.73)<br />
Described below are the types and calculations GenSize uses for the various<br />
miscellaneous loads:<br />
Welder Load Calculations<br />
RkW If RkVA entered: RkW = RkVA x RPF<br />
If Ramps entered: 1∅ RkW = (Ramps x voltage x RPF) ÷ 1000<br />
3∅ RkW = (Ramps x voltage x RPF x 1.73) ÷ 1000<br />
RkVA If Ramps entered: RkVA = RkW ÷ RPF<br />
RPF Running power factor as entered or default<br />
SkW SkW = RkW<br />
SkVA SkVA = SkW ÷ SPF<br />
PkW PkW = PkVA x SPF<br />
PkVA As entered, or 1∅ PkVA = (Pamps x voltage) ÷ 1000<br />
3∅ PkVA = (Pamps x voltage x 1.73) ÷ 1000<br />
SPF SPF = SkVA ÷ SkW<br />
AkW AkW = RkW<br />
Ramps 1∅ Ramps = (RkVA x 1000) ÷ voltage<br />
3∅ Ramps = (RkVA x 1000) ÷ (voltage x 1.73)<br />
General Receptacle Load Calculations<br />
RkW RkW = Entered kW<br />
RkVA RkVA = RkW ÷ RPF<br />
RPF Running power factor as entered or default<br />
SkW SkW = RkW<br />
SkVA SkVA = SkW ÷ SPF<br />
SPF SPF = RPF<br />
PkW PkW = RkW<br />
PkVA PkVA = RkVA<br />
AkW AkW = RkW<br />
Ramps 1∅ Ramps = (RkW x 1000) ÷ (voltage x RPF)<br />
3∅ Ramps = (RkW x 1000) ÷ (voltage x RPF x 1.73)<br />
User Defined Load Calculations<br />
RkW If kW entered: RkW = Kw<br />
If kVA entered: RkW = kVA x RPF<br />
If Ramps entered: 1∅ RkW = (Ramps x voltage x RPF) ÷ 1000<br />
3∅ RkW = (Ramps x voltage x RPF x 1.73) ÷ 1000<br />
RkVA If kW entered: RkVA = RkW ÷ RPF<br />
If RkVA entered: RkVA = kVA<br />
If Ramps entered: 1∅ RkVA = (Ramps x voltage) ÷ 1000<br />
3∅ RkVA = (Ramps x voltage x 1.73) ÷ 1000<br />
A–13