24.01.2013 Views

appendix

appendix

appendix

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

Application Manual – Liquid Cooled Generator Sets<br />

Whenever a reduced voltage starter is used for a fire pump motor, the user should<br />

consider sizing for across–the–line starting because the fire pump controller includes<br />

either a manual–mechanical, manual–electrical, or automatic means to start the pump<br />

across–the–line in the case of a controller malfunction. GenSize will not disallow use of<br />

reduced voltage starters for fire pumps, however.<br />

RkW If HP entered: RkW = HP x 0.746 ÷ Running Efficiency<br />

If kW entered: RkW = kW ÷ Running Efficiency<br />

If Ramps entered: 1∅ RkW = (Ramps x voltage x RPF x Efficiency) ÷ 1000<br />

3∅ RkW = (Ramps x voltage x RPF x Efficiency x 1.73)<br />

÷ 1000<br />

RkVA RkVA = RkW ÷ RPF<br />

RPF Running power factor as entered or default from database<br />

SkW High Inertia SkW = SkVA x SPF<br />

Low Inertia SkW = SkVA x SPF x 0.6<br />

SkVA SkVA = HP x (LRkVA/HP) x SkVA factor, where LrkVA/HP is the average kVA/HP<br />

for the NEMA Code letter of the motor, and SkVA factor is 1.0 for full voltage<br />

starting, or from reduced voltage starting table (see Reduced Voltage Starting<br />

Method)<br />

SPF As entered, or default values from database by HP and starting method<br />

PkW PkW = SkW<br />

PkVA PkVA = SkVA<br />

AkW (non–VFD) AkW = RkW except solid–state starter where AkW = 2.0 x RkW<br />

unless a bypass contactor is used, then AkW = RkW<br />

AkW (VFD) Conventional AC Inverter: AkW = 2.0 x RkW<br />

Pulse Width Modulated: AkW = 1.4 x RkW<br />

DC Drive: AkW = 2.0 x RkW<br />

Ramps 1∅ Ramps = (HP x 746) ÷ (voltage x Efficiency x RPF)<br />

3∅ Ramps = (HP x 746) ÷ (1.73 x voltage x Efficiency x RPF)<br />

UPS Load Calculations<br />

A static UPS uses silicon controlled rectifiers (SCR) or another static device to convert<br />

AC voltage to DC for charging batteries, and an inverter to convert DC to conditioned AC<br />

power to supply the load. A UPS is a non–linear load and may require an oversized<br />

alternator. Some incompatibility problems between generator sets and static UPSs have<br />

led to many misconceptions about sizing the generator set for this type of load. Past<br />

problems did occur, and the recommendation from UPS suppliers at that time was to<br />

oversize the generator set from two to five times the UPS rating. Even then some<br />

problems persisted, and since then those incompatibility problems have been addressed<br />

by most UPS manufacturers. It is more cost effective to require generator compatibility of<br />

the UPS supplier than to oversize the generator.<br />

If the batteries are discharged when the UPS is operating on the generator set, the<br />

generator set must be capable of supplying the rectifier for battery charging and the<br />

inverter to supply the load. A second reason to use the full UPS rating is that additional<br />

UPS load may be added in the future up to the nameplate rating. The non–linear load<br />

sizing factors used by GenSize are based on the level of harmonics the UPS induces in<br />

the generator output with the UPS fully loaded. Since the harmonics increase at lighter<br />

loads, selecting the larger capacity alternator helps to offset this effect.<br />

For multiple redundant UPS systems, size the generator set for the combined nameplate<br />

ratings of the individual UPSs. Redundant system applications are those where one UPS<br />

is installed to back up another and the two are on–line at all times with 50% or less load.<br />

UPS equipment often has varying power quality requirements depending on the operating<br />

mode. When the rectifier is ramping up, often relatively broad frequency and voltage<br />

swings can occur without disrupting equipment operation. However, when the bypass is<br />

enabled, both frequency and voltage must be very constant, or an alarm condition will<br />

A–12 APPENDIX A<br />

Rev. Jan 2011

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!