Fire Fighting Systems and Equipments - Abacus Marine Consultants
Fire Fighting Systems and Equipments - Abacus Marine Consultants
Fire Fighting Systems and Equipments - Abacus Marine Consultants
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
http://www.sea-plus.co.kr<br />
<strong>Fire</strong> <strong>Fighting</strong> <strong>Systems</strong><br />
<strong>and</strong> <strong>Equipments</strong><br />
<strong>Fire</strong> <strong>Fighting</strong> <strong>Systems</strong> <strong>and</strong> <strong>Equipments</strong>
SEAPLUS for your safety life - 2Page<br />
Go with SEAPLUS for your safety of<br />
fire extinguishing systems,<br />
equipments, <strong>and</strong> others<br />
Go with SEAPLUS for your safety of fire extinguishing systems, equipments, <strong>and</strong> others
<strong>Fire</strong> <strong>Fighting</strong> <strong>Systems</strong> <strong>and</strong> <strong>Equipments</strong><br />
Index<br />
Introduction 04Page<br />
Company history 05Page<br />
External fire fighting system 06~07Page<br />
Water mist fire extinguishing system 08~09Page<br />
High expansion foam fire extinguishing system 10Page<br />
Deck foam fire extinguishing system 11Page<br />
High pressure CO2 fire extinguishing system 12Page<br />
Low pressure CO2 fire extinguishing system 13Page<br />
Dry chemical powder fire extinguishing system 14Page<br />
Automatic sprinkler fire extinguishing system 15Page<br />
<strong>Fire</strong> detection & alarm system 16Page<br />
Loose fire fighting equipment 17Page<br />
Quality certification 18Page<br />
Total fire test shop 19Page<br />
World wide a/s net work 20~21Page<br />
Plant project team 22~23Page<br />
SEAPLUS for your safety life - 3Page
SEAPLUS for your safety life - 4Page<br />
GO with SEAPLUS for your safety of<br />
fire extinguishing systems <strong>and</strong> equipments.
Introduction<br />
SEAPLUS CO., LTD. is one of leaders <strong>and</strong> manufacturers for fire fighting<br />
systems & safety equipment in Korea <strong>and</strong> we have taken our expertise &<br />
experience into the world wide market to establish a reputation for<br />
excellence <strong>and</strong> customer support.<br />
We are confident that you will find our presentation of interest <strong>and</strong> assure<br />
you of our competence <strong>and</strong> desire to realize your contract in away totally<br />
satisfactory to you, our prospective client.<br />
Company history<br />
1994 7 Established DAE KYEONG Engineering Co.<br />
1997 4 Incorporated as "SEAPLUS CO., LTD."<br />
1999 7 Acquisition for license of <strong>Fire</strong> protection system construction by Busan city<br />
1999 9 Certified ISO 9001 by KOREAN REGISTER of SHIPPING<br />
2000 4 Moved the factory & office to NOKSAN industrial complex<br />
2001 4 Technical R & D Lab. Approved by KITA<br />
2001 6 Established Total fire test shop<br />
2002 5 Designated as Venture Business<br />
2002 6 Developed Local fire fighting system in According with MSC Circ.913<br />
2002 7 Certified as technology-innovating SME (INNO-BIZ) business by<br />
Small & Medium Business Administration<br />
2003 9 Awarded Presidential citation<br />
2004 12 Awarded Advance Idea Man (New Knowledge Man)<br />
2006 10 Developed Total Application Water mist fire extinguishing system in<br />
According with MSC Circ.1165<br />
2006 12 Selected as "Leading Enterprise in Strategic Industry" by Busan city<br />
2007 8 Chosen as Promising Enterprise by WOORI BANK<br />
2007 10 Developed Self-rotation type high expansion foam generator<br />
2008 7 Established 2nd manufacturing factory<br />
2008 7 Superiority Business man Awarding by Busan city<br />
2008 10 Awarded the Prime Minister<br />
2008 11 Acquisition for license of <strong>Fire</strong> protection system design by Busan city<br />
2008 12 Awarded "Commendation for Genuine S/W User" by Minister of Culture, Sports <strong>and</strong> Tourism<br />
SEAPLUS for your safety life<br />
SEAPLUS for your safety life - 5Page
SEAPLUS for your safety life<br />
In fire fighting system, the external fire fighting system is to extinguish <strong>and</strong> suppress<br />
fires against external vessel. It is equipped with fire monitor, fire fighting pump,<br />
electric motor, portable controller <strong>and</strong> fire monitor <strong>and</strong> so on. <strong>Fire</strong> fighting pump can<br />
be driven by transmission power from driven-engine or dedicated motor.<br />
According to mounting location of fire monitor, there are sliding tower, folding tower<br />
<strong>and</strong> platform on wheel house.<br />
Tower's characteristic is to be folded <strong>and</strong> storaged in a low <strong>and</strong> compact size. It<br />
would significant facilitate h<strong>and</strong>ling on fire suppression <strong>and</strong> extinguishing using dual<br />
monitor of foam liquid <strong>and</strong> dry powder.<br />
External <strong>Fire</strong> <strong>Fighting</strong> System<br />
Water monitor system capacity (ABS Rule 5-9-1/Table.1, 2006)<br />
Class Notation<br />
Number of water monitors<br />
Discharge rate per monitor, m3 /h<br />
Number of pumps<br />
Total capacity, m3 Class<br />
Class<br />
Class<br />
2<br />
3 4<br />
4<br />
1,200<br />
2,400 1,800<br />
2,400<br />
1-2<br />
2-4<br />
2-4<br />
/h<br />
2,400<br />
7,200<br />
9,600<br />
Monitor range, m<br />
120<br />
150<br />
150<br />
Height, monitor, m<br />
45<br />
70<br />
70<br />
Number of hose connection each side of vessel<br />
4<br />
8<br />
10<br />
Number of fireman's outfits<br />
4<br />
8<br />
10<br />
Fuel oil capacity<br />
24<br />
96<br />
96<br />
1) Range : measured horizontally from the monitor outlet to the mean impact area.<br />
2) Height : minimum height of the trajectory of water monitor jet measured vertically from sea level assuming a mean impact area<br />
located at a horizontal distance not less than 70m from the nearest part of the fire fighting vessel.<br />
3) Fuel oil capacity is to include provisions for continuous operation of all monitors in addition to the total capacity<br />
of the vessel's fuel oil tanks required for continuous fire fighting operation. See also 5-9-2/5.<br />
Controller <strong>Fire</strong> Pump Unit<br />
SEAPLUS for your safety life - 6Page
Model<br />
FE-65<br />
FE-80<br />
FE-100<br />
FE-125<br />
FE-150<br />
FE-200<br />
FE-200D<br />
SFE-200<br />
SFE-200S<br />
SFE-200D<br />
SFE-200DS<br />
FEH-200<br />
FEH-200D<br />
FEH-250<br />
FEH-300<br />
Folding Tower<br />
Capacity<br />
L/min m3 /h<br />
500 ~ 1,500<br />
1,500 ~ 3,000<br />
3,000 ~ 5,000<br />
5,000 ~ 8,000<br />
8,000 ~ 11,333<br />
11,333 ~ 20,000<br />
11,333 ~ 25,000<br />
25,000 ~ 40,000<br />
40,000 ~ 60,000<br />
30 ~ 90<br />
90 ~ 180<br />
180 ~ 300<br />
300 ~ 480<br />
480 ~ 680<br />
680 ~ 1,200<br />
680 ~ 1,500<br />
1,500 ~ 2,400<br />
2,400 ~ 3,600<br />
Actuating Method Remark<br />
Electric<br />
Electric<br />
Electric<br />
Electric<br />
Electric<br />
Electric<br />
Electric<br />
Electric<br />
Electric<br />
Electric<br />
Electric<br />
Electro-Hydraulic<br />
Electro-Hydraulic<br />
Electro-Hydraulic<br />
Electro-Hydraulic<br />
Discharge of <strong>Fire</strong> Monitor<br />
Sliding Tower<br />
Portable Controller<br />
Double Gun<br />
Double Gun<br />
Double Gun<br />
Double Gun<br />
SEAPLUS for your safety life - 7Page
SEAPLUS for your safety life<br />
Water Mist Skid(Low)<br />
Water Mist Skid(High)<br />
SEAPLUS for your safety life - 8Page<br />
Using spraying water in all fires, the water mist system is to suppress <strong>and</strong> fight all fires in<br />
protected areas. In this fire extinguishing system, water is sprayed in high or low pressure<br />
to make small water droplets. Using water droplets, vaporization effect gets increased as<br />
much as surface area expansion. Water mist is sprayed into flame so that to promote<br />
vaporization <strong>and</strong> decrease in oxygen concentration as suffocation. Extinguishing effect<br />
becomes increased by cooling. The system has two types of local fire fighting system <strong>and</strong><br />
total fire fighting system. Especially, in case of local application, it is designed <strong>and</strong><br />
installed to cover main engine, aux. engine, boiler, incinerator <strong>and</strong> purifiers as protected<br />
area respectively. The arrangements of nozzle will be provided according to capacity of<br />
nozzle in relevant protected area. In case UMA, after fire happens, using fire alarm<br />
system by detecting fire automatically, water mist pump shall be runned. And water is<br />
discharged into fire area through nozzle to extinguish it. During spraying water, audible<br />
<strong>and</strong> visible alarms are provided in the protected space.<br />
Water Mist <strong>Fire</strong> Extinguishing System<br />
Water Mist Controller<br />
Water Mist Controller<br />
Local Operating Box
Local Application System<br />
Model : SPF-1<br />
Model : HSN-510<br />
Model : SPF-3<br />
Total Application System<br />
Working<br />
Pressure (bar)<br />
50 ~ 60<br />
90 ~ 100<br />
Working<br />
Pressure (bar)<br />
K-Factor<br />
(Flow rate)<br />
1.5 (10.6~11.6LPM)<br />
1.5 (14.2~15.0LPM)<br />
K-Factor<br />
(Flow rate)<br />
1.5<br />
2.5<br />
Installation (m)<br />
Spacing Min. Height Max. Height<br />
0.6<br />
3.0<br />
Installation (m)<br />
3.0<br />
8.0<br />
Spacing Min. Height Max. Height<br />
Projection<br />
Vertical Downward<br />
Vertical Downward<br />
Projection<br />
40 ~ 90 1.65 (10.6~44LPM) 4.0 0.6 3.0 Vertical Downward<br />
Working<br />
Pressure (bar)<br />
Model : SPF-1C (Accomodation)<br />
Working<br />
Pressure (bar)<br />
Model : SPF-2 (Engine Room)<br />
K-Factor<br />
(Flow rate)<br />
Min. 7.5 4.76 (13LPM)<br />
50 ~ 60<br />
90 ~ 100<br />
Nozzle<br />
Model<br />
Celling nozzle SPF-2<br />
Bilge nozzle SPF-2<br />
Doorway nozzle SPF-2D<br />
K-Factor<br />
(Flow rate)<br />
1.5 (10.6~11.6LPM)<br />
1.5 (14.2~15.0LPM)<br />
Installation (m)<br />
Spacing Min. Height Max. Height<br />
Projection<br />
Vertical Downward<br />
4.0 0.5 17.0 Inclined angle<br />
(30 ~60 form vertical)<br />
8.0 0.5 5.0 Side Shooting<br />
1.5<br />
2.5<br />
Installation (m)<br />
Spacing Min. Height Max. Height<br />
Working K-Factor Installation (m)<br />
Pressure (bar) (Flow rate) Spacing Location Max. distance to wall<br />
0.46 (3.56LPM) 4.0 4.0 Max. 1.5 below Celling 2.0<br />
60 0.46 (3.56LPM) 3.2 3.2 Bilge plate mounted -<br />
0.21 (1.62LPM) 0.4(tip to tip) Max. 0.3 Above Doorway -<br />
0.6<br />
3.0<br />
3.0<br />
8.0<br />
Projection<br />
Vertical Downward<br />
Vertical Downward<br />
Projection<br />
Vertical<br />
Downward<br />
SEAPLUS for your safety life -9Page
SEAPLUS<br />
for your safety life<br />
High Expansion Foam <strong>Fire</strong> extinguishing system<br />
High expansion foam system is used as alternative system of Halon extinguishing system.<br />
As halon replacement being phased out due to environmental reasons, high expansion foam system is good<br />
replacement. It is also excellent alternative system of CO2 <strong>and</strong> sprinkler systems. High expansion foam system is<br />
suitable for installation in engine room together with adjacent spaces as local <strong>and</strong> /or total flooding. The system is<br />
manually operated but may be supplied upon request with remote operation.<br />
High expansion foam system has been extensively full scale tested for fires in machinery spaces,<br />
class 1, 2&3, following IMO guidelines. High expansion foam system<br />
extinguishes fires with a combination of water <strong>and</strong> foam. Foam fills all<br />
the voids <strong>and</strong> seals the fire from the air supply, <strong>and</strong> steam absorbs<br />
heat energy when water is vaporized. An inert atmosphere is created<br />
<strong>and</strong> the fire is extinguished. When a fire occurs, fire fighting can<br />
immediately begin by the user of high expansion foam system <strong>and</strong> there<br />
is a further advantage of reduced damage due to the cooling effect<br />
created by the water <strong>and</strong> the foam on surfaces.<br />
When installing high expansion foam system there is no need for large air<br />
ducts or unnatural hull opening to produce foam. simplified piping system <strong>and</strong> low<br />
weight generators in combination with seaplus traditionally <strong>and</strong> well proven foam<br />
central unit makes the whole system easy to install.<br />
Foam Generator<br />
High Expansion Foam Generator V : Vertical downward H : Horizontal<br />
Model<br />
SPHG-30<br />
SPHG-60<br />
SPHG-90<br />
SEAPLUS for your safety life - 10Page<br />
Foam Solution<br />
Flow rate(LPM)<br />
32<br />
75<br />
110<br />
Foam Capacity<br />
(m 3 /min)<br />
>28<br />
>65<br />
>96<br />
SPECIFICATION<br />
1) High Expansion Foam Concentrate : Meteor P +, Skum<br />
2) Mixing Ratio : 2% (Foam Concentrate) + 98% (Water)<br />
3) High Expansion Foam Generator<br />
Certification Proportioner<br />
Working<br />
Pressure(Mpa)<br />
0.4<br />
Expansion<br />
Ratio(Times)<br />
V 880 / H 877<br />
V 877 / H 874<br />
V 874 / H 877<br />
Connection<br />
Method<br />
JIS10K-25A<br />
Flange<br />
K-Factor<br />
16.0<br />
37.5<br />
55.0<br />
Weight<br />
(kg)<br />
4<br />
7<br />
10
Deck Foam <strong>Fire</strong> extinguishing system<br />
Foam system for the protection of chemical <strong>and</strong> oil tank decks or heli-decks in accordance with class<br />
requirements <strong>and</strong> IBC code. Calculated <strong>and</strong> designed in accordance with international regulations.<br />
The foam monitors may be delivered as manually operated (electric or hydraulic type).<br />
Foam Hose Box<br />
Foam Monitor<br />
Foam Tank Unit Balanced Pressure mixer<br />
Foam Proportioner<br />
Model<br />
Max. Water Flow<br />
Rate (LPM)<br />
Connection Size<br />
Water Side Foam Side<br />
50F - 100W 3,000 JIS10K-100A JIS10K-50A<br />
50F - 150W 6,000 JIS10K-150A JIS10K-50A<br />
80F - 200W 13,000 JIS10K-200A JIS10K-80A<br />
80F - 250W<br />
Foam Monitor<br />
20,000 JIS10K-250A JIS10K-80A<br />
Model Capacity (LPM) Connection Size<br />
FM - 65<br />
500 ~ 1,500<br />
JIS10K-65A<br />
FM - 80<br />
1,500 ~ 3,000<br />
JIS10K-80A<br />
FM - 100<br />
3,000 ~ 5,000 JIS10K-100A<br />
FM - 125<br />
5,000 ~ 8,000 JIS10K-125A<br />
SEAPLUS for your safety life - 11Page
SEAPLUS<br />
for your safety life<br />
SEAPLUS for your safety life - 12Page<br />
High Pressure CO2 <strong>Fire</strong> extinguishing system<br />
Carbon Dioxide(CO2) Gas, the fastest <strong>and</strong> most efficient extinguishing agent against fires in protected spaces,<br />
suffocates the fire within designated time <strong>and</strong> minimize the damage in protected spaces.<br />
The <strong>Fire</strong> Extinguishing System extinguishes the fire by means of CO2 gas. The system consists essentially of CO2<br />
cylinders, main isolating valve(s), manifold, CO2 nozzles in compartment protected space, <strong>and</strong> pipe lines connecting<br />
these main parts. The system is to be designed by the required discharging time, CO2 cylinders quantity <strong>and</strong> which are<br />
stored in a independent CO2 room. For further security in ship's cargo holds, a smoke detection system can be<br />
combined with the CO2 system. CO2 gas, the fastest <strong>and</strong> most efficient extinguishing agent against fires in protected<br />
spaces, suffocates the fire within designated time <strong>and</strong> minimize the damage in protected spaces.<br />
Cylinder Valve<br />
Master Control Cabinet<br />
Pressure Operating Distribution Valve(1”~6”)
Low Pressure CO2 <strong>Fire</strong> extinguishing system<br />
The required quantity of CO2 gas is stored in one or two large tank. The tank unit is furnished with its own<br />
refrigeration machinery to keep the temperature <strong>and</strong> also to adjust the pressure at the correct level.<br />
The system is designed <strong>and</strong> installed so that CO2 gas can be discharged into relevant protected area using valve<br />
control cabinet. At that moment, the required quantity of CO2 gas is adjusted by timer which is installed at relevant<br />
valve control cabinet.<br />
Pressure CO2 Storage Tank<br />
Safety Valve<br />
15~25mm(1/2”~1”)<br />
Safety Valve<br />
3~300mm(1/8”~12”)<br />
Instrument Control Panel<br />
Double Stop Valve<br />
15~32mm(1/2”~1-1/4”) Refrigerator<br />
SEAPLUS for your safety life - 13Page
SEAPLUS<br />
for your safety life<br />
Dry Chemical Powder <strong>Fire</strong> extinguishing system<br />
The SEAPLUS dry powder system is designed specifically for marine application so that<br />
can be met with SOLAS requirements for LPG <strong>and</strong> LNG tankers.<br />
Hose Station Box<br />
SEAPLUS for your safety life - 14Page<br />
Dry Chemical Powder Gun<br />
Model Flow Rate (kg/sec) Shooting Length (m)<br />
Monitor<br />
H<strong>and</strong> Hose Gun<br />
10<br />
16<br />
20<br />
25<br />
3.5<br />
Pneumatic Control Cabinet<br />
Dry Chemical Powder Skid<br />
10<br />
18<br />
23<br />
30<br />
5 ~ 10
Automatic Sprinkler <strong>Fire</strong> extinguishing system<br />
This system is installed in accommodation spaces <strong>and</strong> other service on the vessels such as passenger ships <strong>and</strong> car<br />
ferries. The sprinkler system is the most effective at its early stage in extinguishing fire.<br />
Statistics estimates that about 70% of all fires has been extinguishing by less than three sprinkler heads.<br />
Operation of sprinkler-system<br />
Immediately after fire breaks out in a protected area, the intense heat rises rapidly under ceiling zone.<br />
As soon as the ambient temperature has reached the set release temperature, the glass bulb bursts <strong>and</strong> the sprinkler<br />
is activated. The sprinkler pressure tank contains fresh water, which being discharged into protected area, at a<br />
constant pressure level. When sprinkler nozzles are actuated,<br />
the sprinkler system is activated resulting in a pressure drop<br />
in the sprinkler storage tank.<br />
Water supply is provided with adequate pressure by<br />
dedicated pump set which is arranged to start automatically<br />
when the pressure falls down below set point of the pump's<br />
start-up relay. The sea ensures an inexhaustible supply as fire<br />
extinguishing agents, posing no threat to passenger <strong>and</strong><br />
crew. For safety reasons, the sprinkler pumps can be operated<br />
form the ship's main <strong>and</strong> emergency switchboard.<br />
Sprinkler Nozzle Release<br />
Sprinkler Heads<br />
Nozzle Escutcheons<br />
Sprinkler Central<br />
Panel<br />
SEAPLUS for your safety life - 15Page
SEAPLUS for your safety life<br />
Heat Detector<br />
SEAPLUS for your safety life - 16Page<br />
The fire detection <strong>and</strong> alarm system consists of fire detectors, manual call point, control<br />
panel, repeater <strong>and</strong> alarm device <strong>and</strong> so on.<br />
Upon the receipt of fire <strong>and</strong> fault signals, fire alarm system shall send relevant signals to<br />
alarm monitoring, alarm device <strong>and</strong> VDR with audible <strong>and</strong> visible alarm as well as<br />
indicate fire <strong>and</strong> fault signals on LCD of fire alarm panel with audible alarm.<br />
<strong>Fire</strong> detection Alarm system<br />
<strong>Fire</strong> Alarm Control Panet (JB-QB-4508)<br />
-4 Loops / 508 Addressable Detectors<br />
<strong>Fire</strong> Alarm Repeater (JB-QB-4508R)<br />
Heat Detector<br />
Smoke Detector<br />
Infra Red Type Flame Detector<br />
Manual Call Point<br />
Isolator<br />
<strong>Fire</strong> Alarm Controller <strong>Fire</strong> Alarm Repeater<br />
Flame Detector Manual Call Point<br />
Smoke Detector Isolator
Loose <strong>Fire</strong> <strong>Fighting</strong> Equipment<br />
<strong>Fire</strong> Man’s Outfit <strong>Equipments</strong><br />
<strong>Fire</strong> Suit Air Breathing Apparatus <strong>Fire</strong> Axe With Beit <strong>and</strong> Life Line Safety Lamp<br />
<strong>Fire</strong> Extinguisher<br />
9L Foam 6.8kg CO2 6.5kg Dry Powder<br />
<strong>Fire</strong> Extinguisher (Portable Type)<br />
Sea water <strong>Fire</strong> <strong>Fighting</strong> <strong>Equipments</strong><br />
45L Foam 135L Foam<br />
<strong>Fire</strong> Extinguisher (Wheel Type)<br />
Portable Foam<br />
Applicator Assembly<br />
<strong>Fire</strong> Hose Rack <strong>Fire</strong> Hose Box <strong>Fire</strong> Hose Reel Spanner<br />
International Shore Connection <strong>Fire</strong> Hose With Coupling Jet / Spray Nozzle<br />
SEAPLUS for your safety life - 17Page
Quality Certification<br />
SEAPLUS for your safety life - 18Page
Total <strong>Fire</strong> Test Shop<br />
Scales<br />
Specification IMO Circ.668 CLASS III (Above 3,000 m 3 for large ship)<br />
Length 35 m<br />
Breadth 11 m<br />
Height 12 m<br />
Volume 3,750 m 3<br />
Material Anti-<strong>Fire</strong> Block & Anti-<strong>Fire</strong> Foam<br />
Major Zone Division Total <strong>Fire</strong> Test Area : Machinery Area / Control & Monitoring Room<br />
Control & Monitoring System<br />
Remote Control for : Pump, Valves<br />
Monitoring & Recording Agent Flow & Pressure<br />
F.O. Flow, Pressure & Temperature<br />
Test Shop Atmosphere Temperature<br />
Engine Mock-Up Temperature<br />
O2 Concentration F.O. Spray Nozzle<br />
Test Shop Atmosphere<br />
Analysis Equipment All Data Analysis System<br />
Data Saving on Computer & Print<br />
What Fi-Fi System can test ? What Kind of fire can test ?<br />
CO2 System Oil Spray <strong>Fire</strong> High Pressure (150 bar)<br />
Low Expansion Foam System Low Pressure (7 bar)<br />
High Expansion Foam System Engine Mock-Up<br />
Dry Chemical Powder System Pool <strong>Fire</strong><br />
Water Mist System Class A <strong>Fire</strong><br />
Water Spray System Cabin, Corridor & Public Space <strong>Fire</strong> (Future)<br />
Smoke Sampling System<br />
<strong>Fire</strong> Detection System<br />
Sprinkler System<br />
Portable Extinguisher<br />
Other Water Based Fi-Fi System<br />
SEAPLUS for your safety life<br />
SEAPLUS for your safety life - 19Page
WORLD WIDE A/S NET WORK<br />
SEAPLUS makes the future with the challenge to a new world <strong>and</strong><br />
unswerving R & D efforts. You shall be assured of our efforts for the world-highest precision <strong>and</strong> quality.<br />
VIKING LIFE-SAVING EQUIPMENT A/S (HEAD OFFICE)<br />
Saedding Ringvej 13 6710 Esbjerg V Denmark<br />
CONTACT : Mr. Jan Nikolaj Jensen<br />
TEL : +45 76 118100, FAX : +45 76 118101<br />
[ SEAPLUS share the following world-wide service station with VIKING A/S]<br />
USA - Miami, California, Cape Canaveral, Washington<br />
FRANCE - Montivilliers, Vitrilles<br />
NORWAY - Straume, Oslo, Avladsnes, Alesund<br />
TURKEY - Tuzla/Istanbul<br />
FINLAND - Lieto<br />
RUSSIA - Petersburg<br />
SWEDEN - Stockholm<br />
ESTONIA - Tallinn<br />
UAE - Dubai<br />
SPAIN - Cadiz, Puxeiros-Mos-Vigo, Barcelona<br />
SOUTH AFRICA - Cape Town, Durban<br />
ICELAND - Hafnafjordur<br />
NETHERLANDS - LX Zwijndrecht, El Harlem, Delfzijl<br />
BELGIUM - Lokeren<br />
ITALY - Napoli, La Spezia, Messina<br />
SINGAPORE<br />
MALAYSIA - Johor Darul Takzim<br />
DENMARK - Esbjerg<br />
GERMANY - Hamburg, Bremerhaven<br />
HONG KONG - Kwai Chung, N.T.<br />
SEAPLUS for your safety life - 20Page
CHINA<br />
OCEAN MARINE SERVICE CO., LTD<br />
No. 1100 Wuzhong Road, Minhang Qi, Shanghai, China<br />
CONTACT : Mr. J.G.Choi<br />
TEL : +86 21 5422 4157, FAX : +86 21 5422 4156<br />
E-MAIL : jgchoi777@dreamwiz.com<br />
HAI CHEUNG TRADING CO. (HK) LTD<br />
Shanghai Representative office<br />
8/F, Ju Yang Tower, No. 1200 Pudong Avenue, Shanghai,<br />
China, 200135<br />
CONTACT : Mr. Gus Hou<br />
TEL : +86 21 6888 9889, FAX : +86 21 6329 3888<br />
E-MAIL : gus_hou@haicheung.com<br />
JAPAN<br />
PRO-TECH Co.,Ltd.<br />
1-6, Taisho-cho 6-Chome, 1 mabari, Ehime, 794-0025, Japan<br />
CONTACT : Mr. Hiroki Kumazawa<br />
TEL : +81 898 23 2051, FAX : +81 898 23 2078<br />
E-Mail : h-kumazawa@protech-i.jp<br />
TAIWAN<br />
Go with SEAPLUS for your s a f e t y o f f i r e e x t i n guishinh systems, eguipments, <strong>and</strong> others<br />
PILOT MARINE TECHNOLOGY &<br />
ENGINEERING CO.,LTD.<br />
No.217, Hsing Sheng Road, Chuan Cheng Dist. Kaohsiung,<br />
Taiwan. R.O.C.<br />
CONTACT : Mr. Johny Wan<br />
TEL : +886 7 8211545, FAX : +866 7 8211571<br />
E-MAIL : pilotm@s9.hinet.net<br />
SINGAPORE<br />
W.H BRENNAN & CO PTE. LTD.<br />
47 Loyang Way, Singapore 508739<br />
CONTACT : Mr. Desmond Goh<br />
TEL : +65 6549 5111, FAX : +65 6542 5246<br />
E-MAIL : demond@whbrennan.com<br />
GERMANY<br />
MK-MARINE GMBH<br />
Werner Oltersdorf Westkai 50, D-27572, Bremerhaven, Germany<br />
CONTACT : Mr. Werner Oltersdorf<br />
TEL : +49 471 97227 13, FAX : +49 471 97227 27<br />
E-MAIL : contact@mk-marine.net<br />
FIREFLY<br />
Am Redder 1<br />
22941 Bargteheide, Germany<br />
CONTACT : Mr. Merijn Struijs<br />
TEL : +49 (0) 4352 20 48 911, FAX : +49 (0) 4352 20 48 920<br />
E-MAIL : merijn.struijs@fire-fly.eu<br />
NETHERLAND<br />
MK-MARINE GMBH<br />
Inglasco <strong>Fire</strong> System B.V, Gounderakstraat 22,<br />
307 DB Rotterdam, Netherl<strong>and</strong>s<br />
CONTACT : Mr. John Fongers<br />
TEL : +31 10 479 3611, FAX : +31 10 479 2355<br />
E-MAIL : info@inglasco.nl<br />
U.A.E<br />
MAXELL INTERNATIONAL L.L.C<br />
P.O BOX 47620, DUBAI, U.A.E<br />
CONTACT : Mr. N.S. PAI<br />
TEL : +971 4 2676128, FAX : +971 4 2676129<br />
E-MAIL : maxell12@emirates.net.ae<br />
TURKEY<br />
GANI SHIP SPARE LTD<br />
Gumussuyu Mah, Kutlu Sok. No. 834437 Taksim Istanbul, Turkey<br />
CONTACT : Ms. Sinem SANDIKCI<br />
TEL : +90 212 293 4477, FAX : +90 212 293 4478<br />
E-MAIL : gani-nb@gani.com.tr<br />
SEAPLUS for your safety life - 21Page
SEAPLUS Plant Project Team<br />
SEAPLUS for your safety life -22Page<br />
DESIGN & CONSTRUCTION for FIRE FIGHTING SYSTEM of PLANT PROJECT<br />
Seaplus’s Plant project team consists of specialists for mechanics, electronics, thermodynamics<br />
<strong>and</strong> fluid mechanics based fire fighting system.<br />
Plant project team has delivered to all Korean thermal power plant a fire fighting system & fire<br />
alarm <strong>and</strong> fire detection system for parts of bulk material h<strong>and</strong>ling system <strong>and</strong> boiler system after<br />
2003 year. We have licenses for fire fighting design <strong>and</strong> construction approved by Korean<br />
government.<br />
We accepted an order for the fire fighting system of Cuba DPP project <strong>and</strong> the service gas supply<br />
system of Bahrain IWPP project recently.<br />
Plant Project Team<br />
FIRE FIGHTING SYSTEM<br />
- CO2 SYSTEM<br />
- DRY CHEMICAL SYSTEM<br />
- WATER SPRAY SYSTEM<br />
- CLEAN AGENT SYSTEM<br />
- SPRINKLER SYSTEM<br />
- WATER SPRAY SYSTEM<br />
- FOAM SYSTEM<br />
- HYDRANT SYSTEM<br />
FIRE ALARM & FIRE DETECTION SYSTEM<br />
KDX-III DELUGE & SPRINKLER SYSTEM
Seaplus plant project team plans, designs, manufactures <strong>and</strong> supplies a full range of proprietary products for dust<br />
suppression, return belt washing <strong>and</strong> water spray system. Plusgun dust suppression system consists of the PLC based<br />
control system <strong>and</strong> a shooting gun which spray water on the ground uniformly. Plus dust suppression system is<br />
focused on developing intelligent solutions for the flying ash at raw material storage area like as coal, coke <strong>and</strong> scrap<br />
iron etc or inside chute <strong>and</strong> skirt in transfer tower. Return belt washing system for protect to stack a raw material on<br />
the floor in gallery or girder is applied to bulk material h<strong>and</strong>ling system.<br />
PLUS GUN DUST SUPPRESSION SYSTEM<br />
PLC BASED CONTROL SYSTEM<br />
WATER SPRAY SYSTEM<br />
Water spray system is designed to direct water at a required density, from nozzles having predetermined patterns to<br />
completely impinge water onto the hazard surface being protected. It is designed for use in a variety of special<br />
hazards applications including flammable <strong>and</strong> combustible liquid hazards, transformers <strong>and</strong> turbines.<br />
SERIVCE GAS SUPPLY SYSTEM<br />
Service gas system applied to steam power generator. Nitrogen (N2) gas system shall be to blanket the steam <strong>and</strong><br />
water line in order to prevent corrosion during long term wet lay up. Carbon Dioxide (CO2) gas system is used for<br />
purging the air <strong>and</strong> other gases in pipe system. Hydrogen (H2) gas system is used as a coolant for the main steam<br />
turbine or generators.<br />
SEAPLUS for your safety life - 23Page
ADD 1575-3, SongJeong-Dong GangSeo-gu Busan Korea<br />
TEL +82-51-831-0119<br />
FAX +82-51-831-1119<br />
E-mail Domestic /seasales@sea-plus.co.kr<br />
Overseas /overseas@sea-plus.co.kr<br />
Plant /l<strong>and</strong>sales@sea-plus.co.kr<br />
A/S /as@sea-plus.co.kr<br />
http://www.sea-plus.co.kr<br />
Rev. No. 200905 Vol. 1