FORM 201.28-NM1.1<br />

ISSUE DATE: 8/29/2012<br />

SYS X PULLDOWN MOTOR CURRENT LIMITING<br />

The pulldown motor current limiting message indicates<br />

the pulldown motor current load limit or pulldown<br />

motor current unloading is in effect based on the programmed<br />

setpoint.<br />

SYS X ISN CURRENT LIMITING<br />

The ISN Current Limiting message indicates the motor<br />

current load limit or motor current unloading is in effect<br />

through the use of the YORKTalk setpoint.<br />

SYS X REMOTE MOTOR CURRENT LIMITING<br />

The Remote Motor Current Limiting message indicates<br />

the motor current load limit or motor current unloading<br />

is in effect through the use of the remote setpoint offset.The<br />

setpoint may be offset using a remote voltage<br />

or a current signal. The remote current limit must be<br />

activated for this function to operate.<br />

SYS X VSD BASEPLATE TEMP LIMITING<br />

The VSD Baseplate Temp Limiting message indicates<br />

the VSD Baseplate temp is high and load limit or unloading<br />

is in effect.<br />

SECTION 8 - MICROPANEL<br />

SYS X VSD INTERNAL AMBIENT TEMP LIMITING<br />

The VSD Internal Ambient Temp Limiting message indicates<br />

the VSD internal ambient temp is high and load<br />

limit or unloading is in effect.<br />

SYS X SOUND LIMITING<br />

The sound limiting message indicates the sound load<br />

limit is in effect based on the locally programmed<br />

sound limit from the keypad. The sound limit must be<br />

activated for this function to operate.<br />

SYS X ISN SOUND LIMITING<br />

The ISN sound limiting message indicates the sound<br />

load limit is in effect based on the ISN transmitted<br />

sound limit setpoint. The sound limit must be activated<br />

for this function to operate.<br />

SYS X REMOTE SOUND LIMITING<br />

The Remote sound limiting message indicates the<br />

sound load limit is in effect based on the Remote controlled<br />

sound limit setpoint. The setpoint may be offset<br />

using a remote voltage or current signal. The sound<br />

limit option must be activated for this function to operate.<br />

JOHNSON CONTROLS 97<br />