FORM 201.28-NM1.1<br />

ISSUE DATE: 8/29/2012<br />

Low Ambient Temp Fault<br />

If the ambient temperature falls below the programmable<br />

Low Ambient Temp Cutout the chiller will shut<br />

down with a controlled ramped shutdown. This fault<br />

will only occur if the Low Ambient Cutout is “EN-<br />

ABLED” under the OPTIONS key. Restart can occur,<br />

if demand allows, when temperature rises 1.1°C (2°F)<br />

above the cutout. This fault cannot cause a lockout.<br />

The fault display message will be present only during<br />

the time when the ambient temperature is causing a<br />

fault condition. A sample display is shown below:<br />

UNIT YYYYYYYY<br />

LOW AMBIENT TEMP<br />

The unit is also inhibited from starting any time the<br />

temperature is below the cutout plus 1.1°C (2°F).<br />

Low Leaving Chilled <strong>Liquid</strong> Temp Fault<br />

The Low Leaving Chilled <strong>Liquid</strong> Temp Cutout helps to<br />

protect the chiller from an evaporator freeze-up should<br />

the chilled liquid temp drop below the freeze point.<br />

This situation could occur under low flow conditions<br />

or if the Micro Panel setpoint values are improperly<br />

programmed. Any time the leaving chilled liquid temperature<br />

(water or brine) drops below the programmable<br />

cutout point, the chiller will fault and shutdown<br />

with a controlled ramped shutdown. Restart can occur,<br />

if demand allows, when chilled liquid temperature rises<br />

2.2°C (4°F) above the cutout. This fault cannot cause a<br />

lockout. A sample shutdown message is shown below:<br />

UNIT YYYYYYYY<br />

LOW LEAVING CHILLED LIQUID TEMP<br />

The unit is inhibited from starting any time the chilled<br />

liquid temperature is below the cutout plus 2.2°C (4°F).<br />

VSD Communications Failure Fault<br />

The VSD Communications Failure is to prevent the<br />

unit from trying to run, if the Chiller Control Board<br />

never initializes communications with the VSD Logic<br />

Board. The unit will also shut down with a controlled<br />

ramped shutdown if the Chiller Control Board loses<br />

communications with the VSD Logic Board while the<br />

chiller is operating.<br />

On power-up, the Chiller Microprocessor Board will<br />

attempt to initialize communications with the VSD<br />

Logic Board. The control panel will request data from<br />

the VSD, which includes the number of compressors<br />

and the VSD software version. Once these data points<br />

have been received by the Chiller Control Board, and<br />

SECTION 7 - OPERATION<br />

have been successfully initialized, the Chiller Control<br />

Board will not request them again. If the comms connection<br />

fails to occur and a reply from the VSD Logic<br />

Board does take place in 8 seconds, the Chiller Control<br />

Board will prevent the chiller from operating and a<br />

fault message will be displayed.<br />

During normal operation, if the control panel Chiller<br />

Control Board receives no valid response to messages<br />

for 8 seconds, the unit will shut down all compressors<br />

on a Comms fault. The Chiller Control Board will continue<br />

to send messages to the VSD while faulted. The<br />

unit will be inhibited from starting until communications<br />

is established. The fault will automatically reset<br />

when the Chiller Control Board receives a valid response<br />

from the VSD for a data request. Shown below<br />

is an example of a Comms Failure fault message:<br />

UNIT YYYYYYYY<br />

VSD COMMUNICATIONS FAILURE<br />

SYSTEM SAFETIES (FAULTS)<br />

System Safety (Fault) Operation<br />

System safeties are faults that cause individual systems<br />

to be shut down if a safety threshold is exceeded for 3<br />

seconds. System faults are auto reset faults in that the<br />

system will be allowed to restart automatically after the<br />

120 second anti-recycle timer times out. The only exception<br />

is after any 3 faults on the same system occur<br />

within 90 minutes, that system will be “locked out” on<br />

the last fault. The lockout condition requires a manual<br />

reset using the system switch. The respective system<br />

switch must be cycled OFF and ON to clear the lockout<br />

fault.<br />

When multiple systems are operating and a system<br />

fault occurs, the running systems will ramp down and<br />

the faulted system will be shut OFF and the previously<br />

operating will restart if required after the fault clears<br />

and/or the 120 second anti-recycle timer times out.<br />

In the descriptions of the fault displays that follow, the<br />

fault message will show a YYYYYYYY to indicate<br />

that a system is in a “FAULT” condition and will restart<br />

when the fault clears, or “LOCKOUT” and will<br />

not restart until the operator clears the fault using the<br />

keypad. If a system safety is in effect, the message will<br />

be displayed to the operator when the STATUS key is<br />

pressed.<br />

In some cases, a control panel fault will occur after<br />

a VSD fault, possibly during system shutdown or at<br />

some later time. This is known as an “ALL FAULT”<br />

JOHNSON CONTROLS 89<br />