SECTION 7 - OPERATION<br />

If a low battery condition exists, all programmed<br />

setpoints, program values, time, schedule, and history<br />

buffers will have been lost. These values will all be reset<br />

to their default values, which may not be the desired<br />

operating values. Once a bad battery is detected, the<br />

unit will be prevented from running until the MANU-<br />

AL OVERRIDE key is pressed. Once the MANUAL<br />

OVERRIDE key is pressed, the anti recycle timers will<br />

be set to the programmed default anti recycle time to<br />

allow the operator sufficient time to check setpoints,<br />

program values, etc.<br />

If a low battery is detected, it should be replaced as<br />

soon as possible. The programmed values will all be<br />

lost and the unit will be prevented from running on the<br />

next power interruption.<br />

Invalid Number of Compressors Warning<br />

The INVALID NUMBER OF COMPRESSORS SE-<br />

LECTED Warning will occur after the VSD has been<br />

initialized, if no ”Number of Compressors Select”<br />

jumpers are installed or if more than 1 jumper is installed.<br />

The following warning message will be displayed<br />

indefinitely.<br />

88<br />

UNIT WARNING:<br />

INVALID NUMBER OF COMPRESSORS SELECTED<br />

To clear this warning, both the control panel and VSD<br />

control voltage must be turned OFF and the jumpers<br />

properly installed in the VSD wiring harness.<br />

These jumpers are factory installed in the<br />

wire harness plug and should not require<br />

changes.<br />

Invalid Serial Number Warning<br />

If the INVALID SERIAL NUMBER message appears,<br />

immediately contact <strong>Johnson</strong> <strong>Controls</strong> Product Technical<br />

Support. The appearance of this message may mean<br />

the chiller has lost important factory programmed information.<br />

The serial number can be entered using the<br />

SERVICE key.<br />

UNIT WARNING: INVALID SERIAL NUMBER<br />

ENTER UNIT SERIAL NUMBER<br />

This status message can be bypassed to view additional<br />

messages under the STATUS key by pressing the STA-<br />

TUS key repeatedly to scroll through as many as three<br />

STATUS messages that could possibly be displayed at<br />

any time.<br />

UNIT SAFETIES<br />

FORM 201.28-NM1.1<br />

ISSUE DATE: 8/29/2012<br />

Unit Safety Operation<br />

Unit faults are safeties that cause all running compressors<br />

to be shut down, if a safety threshold is exceeded<br />

for 3 seconds. Unit faults are recorded in the history<br />

buffer along with all data on the unit and system operating<br />

conditions. Unit faults are auto reset faults where<br />

the unit will be allowed to restart automatically after<br />

the fault condition is no longer present. The only exception<br />

is any of the VSD related unit faults. If any 3<br />

VSD unit faults occur within 90 minutes, the unit will<br />

be locked out on the last fault. A VSD lockout condition<br />

requires a manual reset using the system switches.<br />

Both system switches must be cycled OFF and ON to<br />

clear a VSD unit lockout fault. If a unit safety is in<br />

effect, the message will be displayed to the operator<br />

when the STATUS key is pressed.<br />

In the descriptions of the fault displays that follow, the<br />

fault message will show a YYYYYYY to indicate that a<br />

system is in a “FAULT” condition and will restart when<br />

the fault clears or LOCKOUT” and will not restart until<br />

the operator clears the fault using the keypad.<br />

If a control panel safety occurs after the VSD fault, but<br />

before the fault is reset, the control panel fault is an<br />

ALL FAULT of the VSD fault, meaning it will be registered<br />

as such in the History because it occurred while<br />

the VSD was shutting down or while the systems were<br />

shut down. All faults do not store operating data at the<br />

time of the fault.<br />

If a “VSD” fault occurs during the fault rampdown or<br />

while the systems are shut down, the VSD fault will<br />

be registered as a new fault. The reason for this is the<br />

belief any VSD fault should be registered with a full<br />

account of the systems data at the time of the fault.<br />

High Ambient Temp Fault<br />

If the ambient temperature rises above 54°C (130°F),<br />

the chiller will shut down with a controlled ramped<br />

shutdown. Restart will automatically occur, if demand<br />

allows, when temperature falls 1.1°C (2°F) below the<br />

cutout (52.9°C[128°F]). This fault cannot cause a lockout.<br />

The fault display message will be present only during<br />

the time when the ambient temperature is causing a<br />

fault condition. A sample display is shown below:<br />

UNIT YYYYYYYY<br />

HIGH AMBIENT TEMP<br />

The unit will also be inhibited from starting any time<br />

the temperature is above 52.9°C (128°F).<br />