21.01.2013 Views

YVAA Style A Air-Cooled Screw Liquid Chillers ... - Johnson Controls

YVAA Style A Air-Cooled Screw Liquid Chillers ... - Johnson Controls

YVAA Style A Air-Cooled Screw Liquid Chillers ... - Johnson Controls

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

FORM 201.28-NM1.1<br />

ISSUE DATE: 8/29/2012<br />

rator heater is turned OFF. Both evaporator heater outputs<br />

will always be turned ON and OFF together. An<br />

under voltage condition will keep the heater OFF until<br />

full voltage is restored to the system.The heater will<br />

protect the evaporator from freeze-up down to -29°C(-<br />

20°F ).<br />

Compressor Heater Control<br />

Each compressor has its own heater. The purpose of<br />

the heater is to assure refrigerant does not condense<br />

in the compressor. There is no oil sump, but refrigerant<br />

could possibly condense in the rotors or the motor<br />

housing.The heater will be OFF whenever the respective<br />

compressor is running. As soon as the compressor<br />

shuts OFF, the heater will turn ON as long as all motor<br />

temperature sensors in the compressor read less than<br />

70°C (158°F). The heater will turn OFF, if any internal<br />

compressor motor temperature sensor reads more than<br />

71.1°C (160°F).<br />

Alarms<br />

Each system has its own alarm. The Alarm output is ON<br />

(dry contact closed) when no fault condition is present<br />

and OFF (dry contact open) to indicate an alarm<br />

situation. The Alarm will be activated (contacts open),<br />

if any of the following are true.<br />

• A System is faulted or inhibited from starting for<br />

more than 5 seconds.<br />

• The Unit is faulted or inhibited from starting for<br />

more than 5 seconds.<br />

• A System is locked out.<br />

• The Unit is locked out.<br />

• Power is removed from the chiller.<br />

Chiller Run Contact<br />

The Chiller Run dry contact is closed whenever any system<br />

is running. It is open when all systems are shut OFF.<br />

Flow Switch Control<br />

A chilled liquid flow switch of suitable type MUST be<br />

connected between Terminals 2 and 13 of 1TB to provide<br />

protection against loss of liquid flow, which will<br />

cause evaporator freeze-up if the chiller is permitted<br />

to run.<br />

Remote Run / Stop<br />

A Remote Run/Stop input is available for each system.<br />

BASIC OPERATING SEQUENCE<br />

Start Sequence and Loading<br />

SECTION 7 - OPERATION<br />

To initiate the start sequence of the chiller, the following<br />

conditions must be satisfied before the precharge<br />

of the DC Bus will take place:<br />

• UNIT SWITCH must be ON.<br />

• At least one System Switch is ON<br />

• Run permissive inputs (Remote Cycling Contacts)<br />

must be closed.<br />

• No unit faults exist.<br />

• No unit start inhibits exist.<br />

• At least one system not faulted or inhibited.<br />

• The Daily Schedule is calling for the chiller to<br />

run.<br />

• The Flow Switch is closed.<br />

• Leaving Chilled <strong>Liquid</strong> Setpoint is above the<br />

Setpoint plus CR (Setpoint High Limit).<br />

Once the precharge takes place, if the anti-recycle timer<br />

is timed out the chiller control system on the Chiller<br />

Control Board will select the number of compressors<br />

to start and begin operation of the compressors. The<br />

compressor(s) speed will be ramped to the minimum<br />

start frequency and increase speed as needed in an effort<br />

to regulate the leaving chilled liquid temperature<br />

to meet the desired Setpoint.Unit Warnings<br />

UNIT WARNING<br />

Unit Warning Operation<br />

Unit warnings are caused when a condition is present<br />

requiring operator intervention to restart the unit.<br />

All setpoints, program values, and options should be<br />

checked before operating the unit. Warnings are not<br />

logged to the history buffer. If a unit warning is in<br />

effect, the message will be displayed to the operator<br />

when the STATUS key is pressed.<br />

Low Battery Warning<br />

The LOW BATTERY WARNING can only occur at<br />

unit power-up. On micropanel power-up, the RTC battery<br />

is checked to see if it is still operational. If it is,<br />

normal unit operation is allowed. If the battery voltage<br />

is determined to be low, the following warning message<br />

is displayed indefinitely.<br />

UNIT WARNING: !! LOW BATTERY !!<br />

CHECK SETPOINTS/PROGRAM/OPTIONS/TIME<br />

JOHNSON CONTROLS 87<br />

7

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!