SECTION 5 - TECHNICAL DATA<br />

70<br />

UPPER<br />

HOUSING<br />

LOWER<br />

HOUSING<br />

NON-SKID<br />

ELASTOMERIC<br />

PAD<br />

(D)<br />

ONE INCH DEFLECTION ISOLATOR INSTALLATION<br />

1. Read the following instructions before beginning<br />

installation.<br />

2. Isolators are shipped fully assembled and are to be<br />

positioned in accordance with the submittal drawings<br />

or as otherwise recommended.<br />

3. Set isolators on floor, housekeeping pad or subbase,<br />

ensuring that all isolators centerlines match<br />

the equipment mounting holes. The VMC group<br />

recommends that the isolator base (“B”) be installed<br />

on a level surface. Shim or grout as required,<br />

leveling all isolator bases to the same<br />

elevation (0.25-inch maximum difference can be<br />

tolerated).<br />

4. Bolt or anchor all isolators to supporting structure<br />

utilizing base slotted holes (“C”).<br />

POSITIONING<br />

PIN (H)<br />

0.25” min - 0.5” max<br />

(C)<br />

(B)<br />

FORM 201.28-NM1.1<br />

ISSUE DATE: 8/29/2012<br />

EQUIPMENT<br />

BASE<br />

(C)<br />

5. Place equipment on top of isolators making sure<br />

that mounting holes of the equipment line up with<br />

isolator positioning pin (“H”).<br />

6. Equipment or machine is at its full operating<br />

weight.<br />

7. Adjust each isolator in sequence by turning spring<br />

adjusting bolt (“D”) one full counterclockwise<br />

turn at a time. Repeat this procedure on all isolators,<br />

one at a time.<br />

8. Continue adjusting each isolator until a minimum<br />

of 0.25” clearance is achieved between the lower<br />

housing and upper housing. (See illustration<br />

above).<br />

9. Fine adjust isolators to level equipment.<br />

JOHNSON CONTROLS