FORM 201.28-NM1.1<br />
ISSUE DATE: 8/29/2012<br />
TABLE 3 - ELECTRICAL LUG DATA (CONT'D)<br />
FIELD WIRING LUGS<br />
<strong>YVAA</strong> MODEL<br />
FRAME COND EVAP<br />
027 8 E<br />
029 5 E<br />
030 3 C<br />
030 5 C<br />
INPUT<br />
VOLTS<br />
INPUT<br />
FREQ<br />
HIGH AIRFLOW/HIGH STATIC CONDENSER FANS<br />
TERMINAL BLOCK<br />
WIRE<br />
PER<br />
PHASE<br />
LUG WIRE<br />
RANGE<br />
200 60 4 #1/0 - 700 kcmil<br />
WIRES<br />
PER<br />
PHASE<br />
230 60 4 #2 - 600 kcmil 4<br />
380 60 3 #2 - 600 kcmil 3<br />
400 50 3 #2 - 600 kcmil 3<br />
460 60 3 #2 - 600 kcmil 3<br />
575 60 2 #2 - 600 kcmil 2<br />
200 60<br />
230 60<br />
380 60 4 #2 - 600 kcmil 4<br />
400 50 4 #2 - 600 kcmil 4<br />
460 60 3 #2 - 600 kcmil 4<br />
575 60 3 #2 - 600 kcmil 3<br />
200 60<br />
230 60<br />
380 60 4 #2 - 600 kcmil 4<br />
400 50 4 #2 - 600 kcmil 4<br />
460 60 3 #2 - 600 kcmil 4<br />
575 60 3 #2 - 600 kcmil 3<br />
200 60<br />
230 60<br />
380 60 4 #2 - 600 kcmil 4<br />
400 50 4 #2 - 600 kcmil 4<br />
460 60 3 #2 - 600 kcmil 4<br />
575 60 3 #2 - 600 kcmil 3<br />
CIRCUIT<br />
BREAKER<br />
* Up to 4 wires per phase, consisting of 2 lugs per phase where each lug can accomodate 2 wires.<br />
LUG<br />
WIRE<br />
RANGE<br />
4/0 - 500<br />
kcmil<br />
3/0 - 400<br />
kcmil<br />
3/0 - 400<br />
kcmil<br />
3/0 - 400<br />
kcmil<br />
#1 - 500<br />
kcmil<br />
#4/0 - 500<br />
kcmil<br />
#4/0 - 500<br />
kcmil<br />
#4/0 - 500<br />
kcmil<br />
#3/0 - 400<br />
kcmil<br />
#4/0 - 500<br />
kcmil<br />
#4/0 - 500<br />
kcmil<br />
#4/0 - 500<br />
kcmil<br />
#3/0 - 400<br />
kcmil<br />
#4/0 - 500<br />
kcmil<br />
#4/0 - 500<br />
kcmil<br />
#4/0 - 500<br />
kcmil<br />
#3/0 - 400<br />
kcmil<br />
SECTION 4 - INSTALLATION<br />
NON-FUSED DIS-<br />
CONNECT SWITCH<br />
WIRES<br />
PER<br />
PHASE<br />
LUG WIRE<br />
RANGE<br />
3 #2 - 600 kcmil<br />
3 #2 - 600 kcmil<br />
3 #2 - 600 kcmil<br />
2 #2 - 600 kcmil<br />
4* #2 - 600 kcmil<br />
4* #2 - 600 kcmil<br />
3 #2 - 600 kcmil<br />
3 #2 - 600 kcmil<br />
4* #2 - 600 kcmil<br />
4* #2 - 600 kcmil<br />
3 #2 - 600 kcmil<br />
3 #2 - 600 kcmil<br />
4* #2 - 600 kcmil<br />
4* #2 - 600 kcmil<br />
3 #2 - 600 kcmil<br />
3 #2 - 600 kcmil<br />
Electrical Data Charts 04 08 2011<br />
JOHNSON CONTROLS 43<br />