SECTION 4 - INSTALLATION<br />

TABLE 3 - ELECTRICAL LUG DATA (CONT'D)<br />

38<br />

FIELD WIRING LUGS<br />

<strong>YVAA</strong> MODEL<br />

FRAME COND EVAP<br />

021 5 C<br />

021 8 C<br />

023 3 B<br />

024 5 C<br />

INPUT<br />

VOLTS<br />

INPUT<br />

FREQ<br />

STANDARD & ULTRA QUIET CONDENSER FANS<br />

TERMINAL BLOCK<br />

WIRES<br />

PER<br />

PHASE<br />

LUG WIRE<br />

RANGE<br />

200 60 4 #2 - 600 kcmil<br />

CIRCUIT<br />

BREAKER<br />

WIRES<br />

PER<br />

PHASE<br />

230 60 4 #2 - 600 kcmil 4<br />

380 60 2 #2 - 600 kcmil 2<br />

400 50 2 #2 - 600 kcmil 2<br />

460 60 2 #2 - 600 kcmil 2<br />

575 60 2 #2 - 600 kcmil 2<br />

200 60 4 #2 - 600 kcmil<br />

230 60 4 #2 - 600 kcmil 4<br />

380 60 2 #2 - 600 kcmil 2<br />

400 50 2 #2 - 600 kcmil 2<br />

460 60 2 #2 - 600 kcmil 2<br />

575 60 2 #2 - 600 kcmil 2<br />

200 60 4 #2 - 600 kcmil<br />

230 60 4 #2 - 600 kcmil 4<br />

380 60 3 #2 - 600 kcmil 3<br />

400 50 3 #2 - 600 kcmil 3<br />

460 60 2 #2 - 600 kcmil 2<br />

575 60 2 #2 - 600 kcmil 2<br />

200 60 4 #2 - 600 kcmil<br />

230 60 4 #2 - 600 kcmil 4<br />

380 60 3 #2 - 600 kcmil 3<br />

400 50 3 #2 - 600 kcmil 3<br />

460 60 2 #2 - 600 kcmil 2<br />

575 60 2 #2 - 600 kcmil 2<br />

* Up to 4 wires per phase, consisting of 2 lugs per phase where each lug can accomodate 2 wires.<br />

LUG<br />

WIRE<br />

RANGE<br />

4/0 - 500<br />

kcmil<br />

#1 - 500<br />

kcmil<br />

#1 - 500<br />

kcmil<br />

#1 - 500<br />

kcmil<br />

#1 - 500<br />

kcmil<br />

4/0 - 500<br />

kcmil<br />

#1 - 500<br />

kcmil<br />

#1 - 500<br />

kcmil<br />

#1 - 500<br />

kcmil<br />

#1 - 500<br />

kcmil<br />

4/0 - 500<br />

kcmil<br />

3/0 - 400<br />

kcmil<br />

3/0 - 400<br />

kcmil<br />

#1 - 500<br />

kcmil<br />

#1 - 500<br />

kcmil<br />

4/0 - 500<br />

kcmil<br />

3/0 - 400<br />

kcmil<br />

3/0 - 400<br />

kcmil<br />

#1 - 500<br />

kcmil<br />

#1 - 500<br />

kcmil<br />

FORM 201.28-NM1.1<br />

ISSUE DATE: 8/29/2012<br />

NON-FUSED<br />

DISCONNECT SWITCH<br />

WIRES<br />

PER<br />

PHASE<br />

LUG WIRE<br />

RANGE<br />

3 #2 - 600 kcmil<br />

3 #2 - 600 kcmil<br />

2 #2 - 600 kcmil<br />

2 #2 - 600 kcmil<br />

3 #2 - 600 kcmil<br />

3 #2 - 600 kcmil<br />

2 #2 - 600 kcmil<br />

2 #2 - 600 kcmil<br />

3 #2 - 600 kcmil<br />

3 #2 - 600 kcmil<br />

3 #2 - 600 kcmil<br />

2 #2 - 600 kcmil<br />

3 #2 - 600 kcmil<br />

3 #2 - 600 kcmil<br />

3 #2 - 600 kcmil<br />

2 #2 - 600 kcmil<br />

Electrical Data Charts 04 08 2011<br />