YVAA Style A Air-Cooled Screw Liquid Chillers ... - Johnson Controls
YVAA Style A Air-Cooled Screw Liquid Chillers ... - Johnson Controls
YVAA Style A Air-Cooled Screw Liquid Chillers ... - Johnson Controls
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
SECTION 4 - INSTALLATION<br />
TABLE 3 - ELECTRICAL LUG DATA<br />
34<br />
FIELD WIRING LUGS<br />
<strong>YVAA</strong> MODEL<br />
FRAME COND EVAP<br />
015 3 B<br />
016 5 B<br />
017 8 C<br />
018 3 A<br />
INPUT<br />
VOLTS<br />
INPUT<br />
FREQ<br />
STANDARD & ULTRA QUIET CONDENSER FANS<br />
TERMINAL BLOCK<br />
WIRES<br />
PER<br />
PHASE<br />
LUG WIRE<br />
RANGE<br />
200 60 4 #2 - 600 kcmil<br />
CIRCUIT<br />
BREAKER<br />
WIRES<br />
PER<br />
PHASE<br />
230 60 4 #2 - 600 kcmil 4<br />
380 60 2 #2 - 600 kcmil 2<br />
400 50 2 #2 - 600 kcmil 2<br />
460 60 2 #2 - 600 kcmil 2<br />
575 60 2 #2 - 600 kcmil 2<br />
200 60 4 #2 - 600 kcmil<br />
230 60 4 #2 - 600 kcmil 4<br />
380 60 2 #2 - 600 kcmil 2<br />
400 50 2 #2 - 600 kcmil 2<br />
460 60 2 #2 - 600 kcmil 2<br />
575 60 2 #2 - 600 kcmil 2<br />
200 60 4 #2 - 600 kcmil<br />
230 60 4 #2 - 600 kcmil 4<br />
380 60 2 #2 - 600 kcmil 2<br />
400 50 2 #2 - 600 kcmil 2<br />
460 60 2 #2 - 600 kcmil 2<br />
575 60 2 #2 - 600 kcmil 2<br />
200 60 4 #2 - 600 kcmil<br />
230 60 4 #2 - 600 kcmil 4<br />
380 60 2 #2 - 600 kcmil 2<br />
400 50 2 #2 - 600 kcmil 2<br />
460 60 2 #2 - 600 kcmil 2<br />
575 60 2 #2 - 600 kcmil 2<br />
* Up to 4 wires per phase, consisting of 2 lugs per phase where each lug can accomodate 2 wires.<br />
LUG<br />
WIRE<br />
RANGE<br />
4/0 - 500<br />
kcmil<br />
#2/0 -<br />
500 kcmil<br />
#2/0 -<br />
500 kcmil<br />
#1 - 500<br />
kcmil<br />
#1 - 500<br />
kcmil<br />
4/0 - 500<br />
kcmil<br />
#2/0 -<br />
500 kcmil<br />
#2/0 -<br />
500 kcmil<br />
#1 - 500<br />
kcmil<br />
#1 - 500<br />
kcmil<br />
4/0 - 500<br />
kcmil<br />
#2/0 -<br />
500 kcmil<br />
#2/0 -<br />
500 kcmil<br />
#1 - 500<br />
kcmil<br />
#1 - 500<br />
kcmil<br />
4/0 - 500<br />
kcmil<br />
#1 - 500<br />
kcmil<br />
#1 - 500<br />
kcmil<br />
#1 - 500<br />
kcmil<br />
#1 - 500<br />
kcmil<br />
FORM 201.28-NM1.1<br />
ISSUE DATE: 8/29/2012<br />
NON-FUSED<br />
DISCONNECT SWITCH<br />
WIRES<br />
PER<br />
PHASE<br />
LUG WIRE<br />
RANGE<br />
2 #2 - 600 kcmil<br />
2 #2 - 600 kcmil<br />
2 #2 - 600 kcmil<br />
2 #2 - 600 kcmil<br />
2 #2 - 600 kcmil<br />
2 #2 - 600 kcmil<br />
2 #2 - 600 kcmil<br />
2 #2 - 600 kcmil<br />
2 #2 - 600 kcmil<br />
2 #2 - 600 kcmil<br />
2 #2 - 600 kcmil<br />
2 #2 - 600 kcmil<br />
3 #2 - 600 kcmil<br />
3 #2 - 600 kcmil<br />
2 #2 - 600 kcmil<br />
2 #2 - 600 kcmil<br />
Electrical Data Charts 04 08 2011<br />
JOHNSON CONTROLS