SECTION 4 - INSTALLATION<br />

POWER SUPPLY WIRING<br />

32<br />

INVERTER 1 INVERTER 2<br />

UNIT MOUNTED CONNECTIONS<br />

STANDARD<br />

CONTROL<br />

TRANSFORMER<br />

LINE<br />

REACTOR<br />

TERMINAL BLOCK<br />

(Circuit Breaker - Opt.)<br />

(Non-Fused Disconnect<br />

Switch - Opt.)<br />

FIELD PROVIDED<br />

UNIT POWER<br />

SUPPLY<br />

Minimum Circuit Ampacity (MCA),<br />

Minimum/Maximum Fuse Size and<br />

Minimum/Maximum Circuit Breaker size<br />

varies on chillers based upon model and<br />

options ordered. Consult YorkWorks or<br />

the chiller data plate for electrical data<br />

on a specific chiller.<br />

UNIT CONTROLS<br />

FIGURE 13 - POWER WIRING - 2 COMPRESSOR CONNECTIONS<br />

EVAPORATOR HEATER<br />

FAN<br />

CONTACTORS<br />

GRD<br />

See Note 1<br />

Voltage Utilization Range<br />

RATED<br />

VOLTAGE<br />

FORM 201.28-NM1.1<br />

ISSUE DATE: 8/29/2012<br />

UTILIZATION RANGE<br />

200/60/3 180-220<br />

230/60/3 208-254<br />

380/60/3 342-402<br />

460/60/3 414-508<br />

575/60/3 520-635<br />

400/50/3 360-440<br />

LD15893<br />

JOHNSON CONTROLS