21.01.2013 Views

YVAA Style A Air-Cooled Screw Liquid Chillers ... - Johnson Controls

YVAA Style A Air-Cooled Screw Liquid Chillers ... - Johnson Controls

YVAA Style A Air-Cooled Screw Liquid Chillers ... - Johnson Controls

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

FORM 201.28-NM1.1<br />

ISSUE DATE: 8/29/2012<br />

The liquid must enter the evaporator at<br />

the inlet connection. The standard inlet<br />

connection for the evaporator is opposite<br />

the control panel end of the evaporator.<br />

A flow switch must be installed in the<br />

customer piping at the outlet of the evaporator<br />

and wired back to the control panel<br />

using shielded cable.<br />

There should be a straight run of piping of at least 5<br />

pipe diameters on either side. The flow switch should<br />

be wired to Terminals 2 and 13 on the 1TB terminal<br />

block. A flow switch is required to prevent damage to<br />

the evaporator caused by the unit operating without adequate<br />

liquid flow.<br />

The flow switch used must have gold plated contacts<br />

for low voltage/current operation. Paddle type flow<br />

switches suitable for 10 bar (150 PSIG) working pressure<br />

and having a 1" N.P.T. connection can be obtained<br />

from <strong>Johnson</strong> <strong>Controls</strong> as an accessory for the unit. Alternatively,<br />

a differential pressure switch fitted across<br />

an orifice plate may be used, preferably of the high/low<br />

limit type.<br />

The chilled liquid pump(s) installed in the piping<br />

system(s) should discharge directly into the unit evaporator<br />

section of the system. The pump(s) may be controlled<br />

by the chiller controls or external to the unit.<br />

Pipework and fittings must be separately supported to<br />

prevent any loading on the evaporator. Flexible connections<br />

are recommended which will also minimize<br />

transmission of vibrations to the building. Flexible<br />

connections must be used if the unit is mounted on<br />

anti-vibration mounts, as some movement of the unit<br />

can be expected in normal operation.<br />

Piping and fittings immediately next to the evaporator<br />

should be readily de-mountable to enable cleaning before<br />

operation, and to facilitate visual inspection of the<br />

exchanger nozzles.<br />

The evaporator must be protected by a<br />

strainer, preferably of 40 mesh, fitted as<br />

close as possible to the liquid inlet connection,<br />

and provided with a means of local<br />

isolation.<br />

SECTION 4 - INSTALLATION<br />

The evaporator must not be exposed to flushing velocities<br />

or debris released during flushing. It is recommended<br />

that a suitably sized bypass and valve arrangement<br />

is installed to allow flushing of the piping system.<br />

The bypass can be used during maintenance to isolate<br />

the heat exchanger without disrupting flow to other<br />

units.<br />

Thermometer and pressure gauge connections should<br />

be provided on the inlet and outlet connections of each<br />

evaporator. Gauges and thermometers are not provided<br />

with the unit and are to be furnished by others.<br />

Drain and air vent connections should be provided at<br />

all low and high points in the piping to permit drainage<br />

of the system and to vent any air in the pipes.<br />

<strong>Liquid</strong> system lines at risk of freezing, due to low ambient<br />

temperatures should be protected using insulation<br />

and heater tape and/or a suitable glycol solution.<br />

The liquid pump(s) may also be used to ensure liquid<br />

is circulated when the ambient temperature approaches<br />

freezing point.<br />

Insulation should also be installed around the evaporator<br />

nozzles. Heater tape of 21 Watts per meter under<br />

the insulation is recommended, supplied independently<br />

and controlled by an ambient temperature thermostat<br />

set to switch ON at approximately 2.2°C (4°F), above<br />

the freezing temperature of the chilled liquid.<br />

The evaporator is protected by heater mats placed under<br />

the insulation, which are powered from the unit<br />

control system power supply. During cold weather<br />

when there is a risk of freezing, chiller power should be<br />

left switched on to provide the freeze protection function<br />

unless the liquid systems have been drained.<br />

Any debris left in the water piping between<br />

the strainer and evaporator could<br />

cause serious damage to the tubes in the<br />

evaporator and must be avoided. Be sure<br />

the piping is clean before connecting it to<br />

the evaporator. Keep evaporator nozzles<br />

and chilled liquid piping capped prior to<br />

installation to assure construction debris<br />

is not allowed to enter.<br />

The installer/user must also ensure that<br />

the quality of the water in circulation is<br />

adequate, without any dissolved gases,<br />

which can cause oxidation of steel or<br />

copper parts within the evaporator.<br />

JOHNSON CONTROLS 25<br />

4

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!