SECTION 9 - MAINTENANCE<br />

TABLE 16 - PRESSURE TRANSDUCER OUTPUT VOLTAGE<br />

(MEASURED SIGNAL TO RETURN AT THE TRANSDUCER)<br />

138<br />

SUCTION PRESSURE TRANSDUCER<br />

(125 PSIG)<br />

FORM 201.28-NM1.1<br />

ISSUE DATE: 8/29/2012<br />

DISCHARGE CONDENSER LIQUID PRESSURE AND<br />

DISCHARGE PRESSURE TRANSDUCER<br />

(400 PSIG)<br />

PRESSURE VOLTAGE PRESSURE VOLTAGE<br />

0 0.50 0 0.50<br />

5 0.66 25 0.75<br />

10 0.82 50 1.00<br />

15 0.98 75 1.25<br />

20 1.14 100 1.50<br />

25 1.30 125 1.75<br />

30 1.46 150 2.00<br />

35 1.62 175 2.25<br />

40 1.78 200 2.50<br />

45 1.94 225 2.75<br />

50 2.10 250 3.00<br />

55 2.26 275 3.25<br />

60 2.42 300 3.50<br />

65 2.58 325 3.75<br />

70 2.74 350 4.00<br />

75 2.90 375 4.25<br />

80 3.06 400 4.50<br />

85 3.22<br />

90 3.38<br />

95 3.54<br />

100 3.70<br />

105 3.86<br />

110 4.02<br />

115 4.18<br />

120 4.34<br />

125 4.50<br />