FORM 201.28-NM1.1<br />
ISSUE DATE: 8/29/2012<br />
TABLE 13 - TROUBLESHOOTING GUIDE (CONT'D)<br />
PROBLEM POSSIBLE CAUSE ACTION<br />
SYSTEM STATUS:<br />
MOTOR<br />
CURRENT<br />
LIMITING<br />
VSD FAULT:<br />
HIGH<br />
BASEPLATE<br />
TEMPERATURE<br />
VSD FAULT:<br />
LOW DC<br />
BUS VOLTAGE<br />
A high motor current anticipatory control has<br />
activated current limiting<br />
Coolant level low. Add coolant.<br />
SECTION 9 - MAINTENANCE<br />
Ambient temperature is high, normal<br />
response from controller<br />
Remote or panel limiting is in effect,<br />
Normal response.<br />
Excess charge in system, adjust charge.<br />
Condenser coils dirty, Clean condenser.<br />
Fans NOT operating. Check fans.<br />
Glycol Pump is defective. Replace Glycol Pump.<br />
VSD Board is defective Replace VSD Logic Board.<br />
IBGT Module is defective. Check defective IGBT Module.<br />
SCR / Diode Module is defective. Check SCR / Diode Module.<br />
SCR Trigger Board is defective. Check SCR Trigger Board.<br />
NOTE: Always remove power to the chiller and assure the DC Bus voltage has bled off.<br />
JOHNSON CONTROLS 135<br />