YVAA Style A Air-Cooled Screw Liquid Chillers ... - Johnson Controls
YVAA Style A Air-Cooled Screw Liquid Chillers ... - Johnson Controls
YVAA Style A Air-Cooled Screw Liquid Chillers ... - Johnson Controls
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
FORM 201.28-NM1.1<br />
ISSUE DATE: 8/29/2012<br />
TABLE 13 - TROUBLESHOOTING GUIDE<br />
PROBLEM POSSIBLE CAUSE ACTION<br />
NO DISPLAY ON CON-<br />
TROL PANEL.<br />
UNIT WILL NOT RUN.<br />
LINE FUSE BLOWS.<br />
CHILLER FAULT:<br />
LOW AMBIENT TEMPERATURE<br />
CHILLER FAULT:<br />
HIGH AMBIENT TEMPERATURE<br />
CHILLER FAULT:<br />
LOW LEAVING CHILLED LIQUID<br />
SYSTEM FAULT:<br />
CONTROL VOLTAGE<br />
SYSTEM FAULT:<br />
HIGH OIL TEMPERATURE<br />
Supply to the Panel is missing.<br />
Line Fuse is blown. Check Fuses.<br />
SECTION 9 - MAINTENANCE<br />
High Voltage to the Chiller is missing.<br />
Check 1FU, 2FU, 4FU, 5FU 17FU, or<br />
19FU.<br />
Check 2T or 10T Transformer.<br />
Chiller Control Board is defective. Replace Chiller Control Board.<br />
Display Board defective. Replace Display Board.<br />
SCR Diode Module is defective. Check SCR/Diode Module.<br />
IBGT Module is defective. Check IBGT Module.<br />
VSD Logic Board is defective. Replace VSD Logic Board.<br />
SCR Trigger Board is defective. Replace SCR Trigger Board.<br />
Ambient temperature is lower than<br />
the programmed operating limit.<br />
Ambient Sensor is defective.<br />
Ambient Temperature is above the<br />
maximum operating limit.<br />
Ambient Sensor is defective.<br />
Leaving chilled liquid temperature drops<br />
faster than the unit can unload.<br />
Chilled Water Sensor is defective.<br />
System Fuse is blown.<br />
Oil Temperature Sensor is defective.<br />
Condenser Fans NOT operating or running<br />
backwards.<br />
Check the programmed cutout and<br />
determine if it is programmed correctly.<br />
Check the panel against the thermometer<br />
reading of ambient temperature.<br />
Check outside air temperature.<br />
Check the Panel Display against<br />
Thermometer reading of Ambient<br />
Temperature at the sensor.<br />
Check for restricted flow.<br />
Check for rapid flow changes.<br />
Water loop is too small.<br />
Flow is below minimum for chiller.<br />
Check Sensor against Temp. Gauge in<br />
water line.<br />
Check Sensor for intermittent operation.<br />
Check Wiring for shorts or opens.<br />
Check respective system Fuse 20FU<br />
or 21FU.<br />
Check Sensor with infrared to determine if<br />
reading is reasonable.<br />
Check Fans.<br />
Coils dirty. Check and clean Coils.<br />
NOTE: Always remove power to the chiller and assure the DC Bus voltage has bled off.<br />
JOHNSON CONTROLS 133<br />
9