21.01.2013 Views

YVAA Style A Air-Cooled Screw Liquid Chillers ... - Johnson Controls

YVAA Style A Air-Cooled Screw Liquid Chillers ... - Johnson Controls

YVAA Style A Air-Cooled Screw Liquid Chillers ... - Johnson Controls

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

SECTION 9 - MAINTENANCE<br />

REFRIGERANT REMOVAL, EVACUATION<br />

AND CHARGING A <strong>YVAA</strong> CHILLER<br />

Refrigerant Removal<br />

The <strong>YVAA</strong> utilizes a flooded evaporator. Extreme care<br />

must be taken when removing refrigerant to prevent<br />

damage to the evaporator and the chiller. Carefully review<br />

the following caution below before proceeding<br />

with the recommended process.<br />

130<br />

Incorrect removal of refrigerant will result<br />

in catastrophic freeze damage to the<br />

evaporator and possible additional damage<br />

to other chiller components. Whenever<br />

there is water in the evaporator, the<br />

chilled liquid pumps must be ON and<br />

circulating liquid through the evaporator<br />

above minimum recommended flow rates.<br />

When liquid refrigerant is being removed,<br />

monitor the pressure and do not allow the<br />

pressure to drop below the freeze point<br />

of the chilled liquid flowing through the<br />

evaporator until all liquid refrigerant has<br />

been removed from the evaporator and<br />

only gas remains. Once all liquid has<br />

been removed, the remaining refrigerant<br />

vapor can be removed while allowing the<br />

pressure to drop below the freeze point<br />

with the pump circulating liquid through<br />

the evaporator.<br />

To remove refrigerant from the evaporator, follow the<br />

procedure below:<br />

1. Turn the chilled liquid pump ON and assure the<br />

flow is above the minimum recommended flow.<br />

2. Assure all manual valves in the system are open.<br />

Open Condenser Drain and Economizer Feed<br />

valves to 100% in the service mode.<br />

3. Connect the recovery unit and a manifold gauge<br />

to the liquid line feeding the eductor. There may<br />

be a valve in the line or a Schrader fitting on the<br />

eductor filter for this purpose.<br />

4. Connect the recovery unit to a recovery cylinder<br />

sitting on an accurate scale. Turn the recovery<br />

unit ON and observe the liquid refrigerant flowing<br />

from the line into the cylinder. The flow of liquid<br />

should be obvious.<br />

FORM 201.28-NM1.1<br />

ISSUE DATE: 8/29/2012<br />

5. Monitor the pressure gauge to assure that the pressure<br />

does not drop below the freeze point of the<br />

chilled liquid. Throttle the flow as needed with the<br />

manifold gauge valves to prevent pressures from<br />

dropping below the freeze point.<br />

6. Continue to remove the liquid refrigerant while<br />

observing the flow and the pressure. Note the<br />

charge in the system based on the nameplate data<br />

to determine when the charge removal is nearly<br />

complete. Monitor the weight of the recovery<br />

cylinder to determine when the cylinder is full.<br />

Change the cylinder as needed.<br />

7. Continue removing refrigerant until liquid is no<br />

longer observed flowing in the manifold hoses.<br />

8. Once the liquid is removed and no longer visible<br />

in the hose, the remaining gas can be pumped out<br />

with the recovery unit while the pressure is allowed<br />

to drop to 0 barg (0 PSIG).<br />

9. Servicing may now be performed on the system<br />

as needed.<br />

Evacuating a System<br />

To evacuate a system, follow the procedure below:<br />

1. Turn the chilled liquid pump ON and assure the<br />

flow is above the minimum recommended flow.<br />

2. Assure all manual values are open. Open the Condenser<br />

Drain (Flash Tank Feed) and Economizer<br />

Valves in the Service Mode to 100 %<br />

3. Connect vacuum hoses to as many points as possible.<br />

Be sure that at least one connection is made<br />

on both the high and low side of the piping. A connection<br />

to the evacuation fitting on the compressor<br />

is also recommended. Evacuate the system to<br />

a minimum of 500 microns. Close the valves at<br />

the evacuation points and assure the pressure in<br />

the chiller does not rise more than 50 microns in<br />

10 minutes. Check for leaks if the pressure rises.<br />

Charging Refrigerant into a System<br />

To charge the system with refrigerant, follow the procedure<br />

below:<br />

1. With all system valves open and the Condenser<br />

Drain and Economizer Valves open to 100% by<br />

manually opening them in the Service Mode,<br />

JOHNSON CONTROLS

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!