SECTION 8 - MICROPANEL<br />

COND DRAIN % OPEN XXX.X %<br />

ECONOMIZER % OPEN XXX.X %<br />

CONDENSER FANS ON 0<br />

CONDENSER FAN SPEED XXX % (vsd)<br />

COMPRESSOR HEATER ON<br />

VI STEP SOLENOID 1 OFF<br />

VI STEP SOLENOID 2 OFF<br />

RUN PERMISSIVE ON<br />

VSD RUN RELAY OFF<br />

VSD SOFTWARE RUN SIGNAL OFF<br />

126<br />

SYSTEM 2 DATA<br />

COMPRESSOR STATUS ON<br />

RUN TIME 0-0-15-26 D-H-M-S<br />

MOTOR CURRENT 104 AMPS 87 %FLA<br />

SUCTION PRESSURE 57 PSIG<br />

DISCHARGE PRESSURE 233 PSIG<br />

OIL PRESSURE 218 PSIG<br />

CONDENSER LIQUID TEMP 42.9 DEGF<br />

DISCHARGE TEMPERATURE 145.5 DEGF<br />

OIL TEMPERATURE 102.8 DEGF<br />

SAT CONDENSER TEMP 31.7 DEGF<br />

SUBCOOLING 11.2 DEGF<br />

SAT DISCHARGE TEMP 112.1 DEGF<br />

DISCHARGE SUPERHEAT 33.4 DEGF<br />

MOTOR TMP XXX.X XXX.X XXX.X DEGF<br />

COMPRESSOR SPEED XXX.X%<br />

FLASH TANK LEVEL < 512 ADC<br />

COND DRAIN % OPEN XXX.X%<br />

ECONOMIZER % OPEN XXX.X%<br />

CONDENSER FANS ON 3<br />

CONDENSER FAN SPEED XXX% (vsd)<br />

COMPRESSOR HEATER OFF<br />

VI STEP SOLENOID 1 OFF<br />

VI STEP SOLENOID 2 OFF<br />

RUN PERMISSIVE ON<br />

VSD RUN RELAY OFF<br />

VSD SOFTWARE RUN SIGNAL OFF<br />

UNIT OPERATING SCHEDULE<br />

S M T W T F S *=HOLIDAY<br />

MON START=00:00AM STOP=00:00AM<br />

TUE START=00:00AM STOP=00:00AM<br />

FORM 201.28-NM1.1<br />

ISSUE DATE: 8/29/2012<br />

WED START=00:00AM STOP=00:00AM<br />

THU START=00:00AM STOP=00:00AM<br />

FRI START=00:00AM STOP=00:00AM<br />

SAT START=00:00AM STOP=00:00AM<br />

HOL START=00:00AM STOP=00:00AM<br />

SOUND LIMIT SCHEDULE<br />

(if enabled)<br />

MON START=00:00AM STOP=00:00AM<br />

TUE START=00:00AM STOP=00:00AM<br />

WED START=00:00AM STOP=00:00AM<br />

THU START=00:00AM STOP=00:00AM<br />

FRI START=00:00AM STOP=00:00AM<br />

SAT START=00:00AM STOP=00:00AM<br />

HOL START=00:00AM STOP=00:00AM<br />

History Data Printout<br />

History printouts, when selected, provide stored data<br />

relating to all specific system and chiller operating<br />

conditions at the time of the fault, regardless of whether<br />

a lockout occurred. History information is stored in<br />

battery-backed memory on the Chiller Control Board<br />

and is not affected by power failures or resetting of<br />

faults. Whenever a fault of any type occurs, all system<br />

operating data is stored in battery-backed memory at<br />

the instant of the fault. The history printout is similar<br />

to the operating data printout except for the change in<br />

the header information shown below:<br />

YORK INTERNATIONAL CORPORATION<br />

SYS 1 YYYYYYY<br />

<strong>YVAA</strong> SCREW CHILLER<br />

HISTORY NUMBER 1<br />

2:04:14 PM 30 APR 11<br />

HIGH DSCH PRESS SHUTDOWN<br />

STATUS AT TIME OF SHUTDOWN<br />

SYS 1 XXXXXXXXXXXXXXXXXXXXXXXXXX<br />

SYS 2 XXXXXXXXXXXXXXXXXXXXXXXXXX<br />

ALL FAULTS<br />

XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX<br />

XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX<br />

The most recent fault will always be stored as HIS-<br />

TORY BUFFER #1.<br />