FORM 201.28-NM1.1<br />

ISSUE DATE: 8/29/2012<br />

A sample of the is shown below. The operating data<br />

printout is a snapshot of current system operating conditions<br />

when the printout was selected. The sample<br />

shows combined printouts of 2, 3, and 4 circuit units.<br />

The actual printout will only show data for the appropriate<br />

chiller type.<br />

Bold italic text below a line of print is not<br />

on the actual printout. Bold italic text<br />

indicates information that may not be<br />

available on all printouts or is additional<br />

information to help explain the difference<br />

in a 2/3 or 4 circuit printout.<br />

Operating Data Printout<br />

SYS 1<br />

YORK INTERNATIONAL CORPORATION<br />

NOT RUNNING<br />

SYS 2<br />

COMPRESSOR RUNNING<br />

<strong>YVAA</strong> SCREW CHILLER<br />

OPERATING DATA<br />

2:04:14 PM 30 DEC 11<br />

OPTIONS<br />

CHILLED LIQUID WATER<br />

LOCAL/REMOTE MODE REMOTE<br />

LEAD/LAG CONTROL AUTOMATIC<br />

REMOTE TEMP RESET DISABLED<br />

REMOTE CURRENT LIMIT 0 TO 10 V<br />

REMOTE SOUND LIMIT 4 TO 20 MA<br />

(if Sound Limiting enabled)<br />

LOW AMBIENT CUTOUT ENABLED<br />

PROGRAM VALUES<br />

SUCT PRESS CUTOUT 44 PSIG<br />

LOW AMBIENT CUTOUT 25.0 DEGF<br />

LEAVING LIQUID CUTOUT 36.0 DEGF<br />

MOTOR CURRENT LIMIT 100 %FLA<br />

PULLDOWN CURRENT LIMIT 100 %FLA<br />

PULLDOWN LIMIT TIME 0 MIN<br />

SUBCOOLING SETPOINT 12.0 DEGF<br />

UNIT ID NUMBER 0<br />

SOUND LIMIT SETPOINT 100%<br />

(if Sound Limiting enabled)<br />

UNIT DATA<br />

SECTION 8 - MICROPANEL<br />

LEAVING LIQUID TEMP 49.0 DEGF<br />

RETURN LIQUID TEMP 58.2 DEGF<br />

TEMP RATE XXX.X DEGF/MIN<br />

COOLING RANGE 42.0+/-2.0 DEGF<br />

REMOTE SETPOINT 44.0 DEGF<br />

AMBIENT AIR TEMP 74.8 DEGF<br />

LEAD SYSTEM SYS 2<br />

FLOW SWITCH ON<br />

EVAPORATOR PUMP RUN ON<br />

EVAPORATOR HEATER OFF<br />

ACTIVE REMOTE CONTROL NONE<br />

OPERATING HOURS 1=XXXXX, 2=XXXXX<br />

START COUNTER 1=XXXXX, 2=XXXXX<br />

SOFTWARE VERSION C.ACS.XX.00<br />

VSD DATA<br />

ACTUAL FREQUENCY XXX.X HZ<br />

COMMAND FREQUENCY XXX.X HZ<br />

DC BUS VOLTAGE XXX VDC<br />

INTERNAL AMBIENT TEMP XXX.X DEGF<br />

COOLING SYSTEM STATUS XXX<br />

BASEPLATE TEMPS XXX XXX DEGF<br />

PRECHARGE SIGNAL XXX<br />

MOTOR OVERLOADS 1/2 XXX XXX AMPS<br />

SOFTWARE VERSION C.VSD.XX.00<br />

UNIT SERIAL NUMBER YYYY XXXZZZ<br />

SYSTEM 1 DATA<br />

COMPRESSOR STATUS OFF<br />

RUN TIME 0- 0- 0- 0 D-H-M-S<br />

MOTOR CURRENT 0AMPS 0 %FLA<br />

SUCTION PRESSURE 125 PSIG<br />

DISCHARGE PRESSURE 131 PSIG<br />

OIL PRESSURE 130 PSIG<br />

CONDENSER LIQUID TEMP 68.4 DEGF<br />

DISCHARGE TEMPERATURE 68.8 DEGF<br />

OIL TEMPERATURE 68.8 DEGF<br />

SAT SUCTION TEMP 71.8 DEGF<br />

SUBCOOLING 3.4 DEGF<br />

SAT DISCHARGE TEMP 74.5 DEGF<br />

DISCHARGE SUPERHEAT 6.3 DEGF<br />

MOTOR TMP XXX.XXXX.XXXX.XDEGF<br />

COMPRESSOR SPEED XXX.X %<br />

FLASH TANK LEVEL > 512 ADC<br />

JOHNSON CONTROLS 125<br />