FORM 201.28-NM1.1<br />

ISSUE DATE: 8/29/2012<br />

Manual Override Key Operation<br />

If the MANUAL OVERRIDE key is pressed during<br />

a schedule shutdown, the STATUS display will display<br />

the message below. This indicates that the Daily<br />

Schedule is being ignored and the chiller will start<br />

when chilled liquid temperature allows, Remote Contacts,<br />

UNIT switch and SYSTEM switches permitting.<br />

This is a priority message and cannot be overridden by<br />

MANUAL OVERRIDE KEY<br />

SECTION 8 - MICROPANEL<br />

MANUAL OVERRIDE<br />

KEY<br />

JOHNSON CONTROLS 123<br />

LD10605<br />

anti-recycle messages, fault messages, etc. when in the<br />

STATUS display mode. Therefore, do not expect to see<br />

any other STATUS messages when in the MANUAL<br />

OVERRIDE mode. MANUAL OVERRIDE is to only<br />

be used in emergencies or for servicing. Manual override<br />

mode automatically disables itself after 30 minutes.<br />

MANUAL OVERRIDE<br />