FORM 201.28-NM1.1<br />

ISSUE DATE: 8/29/2012<br />

OPTIONS REMOTE CURRENT LIMIT INPUT<br />

◄ ► DISABLED<br />

OPTIONS REMOTE CURRENT LIMIT INPUT<br />

◄ ► 0.0 TO 10.0 VOLTS DC<br />

OPTIONS REMOTE CURRENT LIMIT INPUT<br />

◄ ► 2.0 TO 10 VOLTS DC<br />

OPTIONS REMOTE CURRENT LIMIT INPUT<br />

◄ ► 0.0 TO 20.0 MILLIAMPS<br />

OPTIONS REMOTE CURRENT LIMIT INPUT<br />

◄ ► 4.0 TO 20.0 MILLIAMPS<br />

The default setting for Remote Current Reset is DIS-<br />

ABLED. This display will only appear if the remote<br />

current limit option is enabled under the Unit Setup<br />

Mode.<br />

Remote Sound Limit Selection<br />

Remote sound limit from an external source may be<br />

tied directly into the chiller microprocessor board.<br />

OPTIONS REMOTE SOUND LIMIT INPUT<br />

◄ ► XXXXXXXXXXXXXXXXXXXX<br />

Selections may be made for DISABLED (no signal),<br />

0 to10VDC, 2 to 10VDC, 0 to 20ma, and 4 to 20ma.<br />

SECTION 8 - MICROPANEL<br />

OPTIONS REMOTE SOUND LIMIT INPUT<br />

◄ ► DISABLED<br />

OPTIONS REMOTE SOUND LIMIT INPUT<br />

◄ ► 0.0 TO 10.0 VOLTS DC<br />

OPTIONS REMOTE SOUND LIMIT INPUT<br />

◄ ► 2.0 TO 10.0 VOLTS DC<br />

OPTIONS REMOTE SOUND LIMIT INPUT<br />

◄ ► 0.0 TO 20.0 MILLIAMPS<br />

OPTIONS REMOTE SOUND LIMIT INPUT<br />

◄ ► 4.0 TO 20.0 MILLIAMPS<br />

The default setting for Remote Sound Limit is DIS-<br />

ABLED. This display will only appear if the remote<br />

sound limit option is enabled under the Unit Setup<br />

Mode.<br />

Low Ambient Cutout Enable/Disable<br />

The low ambient cutout may be enabled or disabled.<br />

When enabled, the chiller will cut OFF when the low<br />

ambient cutout is reached. When disabled, the chiller<br />

will run at any temperature.<br />

OPTIONS LOW AMBIENT TEMPERATURE CUTOUT<br />

◄ ► ENABLED<br />

OPTIONS LOW AMBIENT TEMPERATURE CUTOUT<br />

◄ ► DISABLED<br />

The default setting for the low ambient cutout will be<br />

ENABLED.<br />

JOHNSON CONTROLS 119<br />