FORM 201.28-NM1.1<br />

ISSUE DATE: 8/29/2012<br />

Options Key Operation<br />

The OPTIONS key provides the user with a display of<br />

unit configuration and the capability to modify the configuration.<br />

These options can only be viewed under the<br />

OPTIONS key. To view the current options settings,<br />

press the OPTIONS key. Each press of the OPTIONS<br />

key or press of the ▲ or ▼ (ARROW) keys will scroll<br />

to the next option setting. The ◄ and ► (ARROW)<br />

keys allow changing the option choices. The � (EN-<br />

TER) key must be pressed after a selection is made to<br />

save the change in memory.<br />

An explanation of each option message is provided below.<br />

Display Language Selection<br />

The display language can be selected for English, Italian,<br />

Polish, Hungarian, German, French, Portuguese,<br />

and Spanish.<br />

OPTIONS DISPLAY LANGUAGE<br />

◄ ► XXXXXXXXXXXXXXXXXX<br />

The default language will be English.<br />

Chilled <strong>Liquid</strong> Cooling Mode Selection<br />

The Chilled liquid cooling mode can be selected for<br />

Water Cooling or low temperature Glycol Cooling.<br />

OPTIONS KEY<br />

SECTION 8 - MICROPANEL<br />

OPTIONS<br />

KEY<br />

JOHNSON CONTROLS 117<br />

LD10605<br />

OPTIONS CHILLED LIQUID COOLING MODE<br />

◄ ► XXXXXXXXXXXXXXXXXX<br />

When Water Cooling is chosen, the chilled liquid temperature<br />

setpoint can only be programmed from 4°C to<br />

21°C (40°F to 70°F).<br />

OPTIONS CHILLED LIQUID COOLING MODE<br />

◄ ► WATER COOLING<br />

When Glycol Cooling is chosen, the chilled liquid<br />

temperature setpoint can be programmed from -12°C<br />

to 21°C (10°F to 70°F).<br />

OPTIONS CHILLED LIQUID COOLING MODE<br />

◄ ► GLYCOL COOLING<br />

The default Chilled <strong>Liquid</strong> Mode will be WATER<br />

COOLING.<br />

Local / Remote Control Mode Selection<br />

Local or Remote Control Mode allows the user to select<br />

the chilled liquid temperature control mode.<br />

OPTIONS LOCAL / REMOTE CONTROL MODE<br />

◄ ► XXXXXXXXXXXXXXXXXX<br />