SECTION 8 - MICROPANEL<br />

Eductor Differential<br />

PROGRAM ◄DEF XXXXX LO XXXXX HI XXXXX<br />

EDUCTOR DIFFERENTIAL = XXX °F<br />

The eductor temperature differential is programmable<br />

from 0°C to 10.0°C (0°F to 50.0°F). The default value<br />

is 5.0°F. The programmed temperature assures the micro<br />

will sense a loss of educator oil flow, if the temperature<br />

differential rises. A small differential of 2.8°C<br />

(5.0°F) is recommended.<br />

Eductor Safety Time<br />

PROGRAM ◄DEF XXXXX LO XXXXX HI XXXXX<br />

EDUCTOR SAFETY TIME = XXXX MIN<br />

The educator safety time allows programming the<br />

time period the system is permitted to run if the safety<br />

threshold is exceeded. The safety time is programmable<br />

for 10 minutes to 1000 minutes with 10 minutes as<br />

the default. A minimum safety time is recommended<br />

to assure the compressor is not starved for oil for long<br />

periods of time due to the educator circuit not siphon-<br />

TABLE 11 - PROGRAMMABLE OPERATING PARAMETERS<br />

116<br />

FORM 201.28-NM1.1<br />

ISSUE DATE: 8/29/2012<br />

ing oil from the evaporator. A minimum time of 10<br />

minutes is recommended as the program point.<br />

Motor Temperature Unload<br />

PROGRAM ◄DEF XXXXX LO XXXXX HI XXXXX<br />

MOTOR TEMPERATURE UNLOAD = XXX °F<br />

The motor temperature unload is programmable from<br />

65.6°C (150.0°F) to 121.1°C 250.0°F. The default value<br />

is 115.5°C (240.0°F). The programmed temperature<br />

assures the micro will sense a rise in motor temperature<br />

due to a lack of compressor cooling. If the temperature<br />

rises above the programmed threshold, the system will<br />

unload the compressor by reducing speed. An unload<br />

temperature of 115.5°C (240.0°F) is recommended to<br />

assure the system does provides maximum capacity.<br />

Default Values<br />

A listing of the low limits, high limits, and default values<br />

for each of the programmable values is noted in<br />

each display and can be found in Table 11. Note that<br />

the Imperial units are exact values while the Metric<br />

units are only approximate.<br />

PROGRAM VALUE MODE LOW LIMIT HIGH LIMIT DEFAULT<br />

Water<br />

24.0 PSIG 36.0 PSIG 24.0 PSIG<br />

Suction Pressure Cutout<br />

Cooling<br />

Glycol<br />

1.65 barg<br />

5.0 PSIG<br />

2.48 barg<br />

36.0 PSIG<br />

1.65 barg<br />

24.0 PSIG<br />

Cooling<br />

0.34 barg 2.48 barg 1.65 barg<br />

Low Ambient Temp. Cutout -<br />

-2.0°F<br />

-18.9°C<br />

50.0°F<br />

10.0°C<br />

25.0°F<br />

-3.9°C<br />

Water<br />

- - 36.0°F<br />

Leaving Chilled <strong>Liquid</strong> Temp. Cutout<br />

Cooling<br />

Glycol<br />

-<br />

11.0°F<br />

-<br />

36.0°F<br />

2.2°C<br />

36.0°F<br />

Cooling<br />

-11.7°C 2.2°C 2.2°C<br />

Motor Current Limit - 30% FLA 103% FLA 103% FLA<br />

Pulldown Motor Current Limit - 30% FLA 100% FLA 100% FLA<br />

Pulldown Motor Current Limit Time - 0 Min 255 Min 0 Min<br />

Condenser Subcooling Setpoint -<br />

0.0°F<br />

0.0°C<br />

20.0°F<br />

11.1°C<br />

5.0°F<br />

2.8°C<br />

Unit ID Number - 0 7 0<br />

Sound Limit Setpoint<br />

Sound Limit<br />

Option Enabled<br />

0% 100% 0%<br />

Eductor Temp Differential -<br />

5.0°F<br />

2.77°C<br />

50.0°F<br />

27.8°C<br />

15.0°F<br />

8.3°C<br />

Eductor Safety Time - 10 Min 1000 Min 30 Min*<br />

Motor Temperature Unload -<br />

150.0°F<br />

65.6°C<br />

250.0°F<br />

121.1°C<br />

240.0°F<br />

115.5°C<br />