SECTION 8 - MICROPANEL<br />

Program Key Operation<br />

Various operating parameters are programmable by the<br />

user. These are modified by pressing the PROGRAM<br />

key and then the � (ENTER) key to enter Program<br />

Mode. A listing of the limits of the programmable values<br />

is found below. Note that the Imperial units are exact<br />

values, while Metric units are only approximate.<br />

The ▲ and ▼ (ARROW) keys are used to scroll<br />

through the user programmable values. A value may be<br />

changed by keying in the new value and pressing the �<br />

(ENTER) key to store the new value in memory. The<br />

cursor will be displayed on the screen when a number<br />

key is pressed. The first line of each message will indicate<br />

the chiller default (DEF) value), lowest acceptable<br />

programmable value (LO), and highest acceptable programmable<br />

value (HI). The user programmable value<br />

is programmed ON in the second line of the message.<br />

When the PROGRAM key is first pressed, the following<br />

display will appear indicating the user is in the program<br />

mode:<br />

PROGRAM MODE XXXX<br />

PRESS ENTER KEY TO CONTINUE<br />

Pressing the � (ENTER) key again will display the<br />

first programmable selection.<br />

114<br />

PROGRAM KEY<br />

FORM 201.28-NM1.1<br />

ISSUE DATE: 8/29/2012<br />

PROGRAM<br />

KEY<br />

LD10605<br />

Suction Pressure Cutout<br />

PROGRAM ◄DEF XXXXX LO XXXXX HI XXXXX<br />

SUCTION PRESSURE CUTOUT = XXX.X PSIG<br />

The suction pressure cutout is protects the chiller from<br />

a low refrigerant condition. It also helps protect from<br />

a freeze-up due to low or no chilled liquid flow. However,<br />

it is only a back-up for a flow switch and cannot<br />

protect against an evaporator freeze under many conditions.<br />

This cutout is programmable and should generally<br />

be programmed for 1.65 barg (24 PSIG) for chilled<br />

water cooling.<br />

The cutout is programmable between 1.65 and 2.48<br />

barg (24.0 and 36.0 PSIG) in the Water Cooling mode<br />

and 0.34 and 2.28 barg (5.0 and 36.0 PSIG) in the Glycol<br />

Cooling mode. The default value for both modes<br />

will be 1.65 barg (24.0 PSIG).<br />

Low Ambient Cutout<br />

PROGRAM ◄DEF XXXXX LO XXXXX HI XXXXX<br />

LOW AMBIENT TEMP CUTOUT = XXX.X °F<br />

The low ambient temp cutout allows programming the<br />

outdoor temperature at which it is desired to shut down<br />

the chiller to utilize other methods of cooling.<br />

The cutout is programmable between -18.9°C (-2.0°F)<br />

and 10.0°C (50°F) with a -3.9°C (25°F) default.<br />