SECTION 8 - MICROPANEL<br />

Setpoints Key Operation<br />

Cooling setpoints and ranges may be programmed by<br />

pressing the SETPOINTS key. The first setpoint entry<br />

screen will be displayed as shown below. The first<br />

line of the display will show the chiller default (DEF),<br />

minimum acceptable value (LO) and maximum acceptable<br />

value (HI). The second line shows the actual<br />

programmed value. Table 10 also shows the allowable<br />

ranges for the cooling setpoints and Control Ranges.<br />

Note that the Imperial units are exact values while the<br />

Metric units are only approximate.<br />

SETPOINTS ◄DEF XXXXX LO XXXXX HI XXXXX<br />

LOCAL COOLING SETPOINT = XXX.X °F<br />

Pressing the SETPOINTS key a second time or the ▼<br />

(ARROW) key will display the leaving chilled liquid<br />

Control Range, default, and low/high limits.<br />

SETPOINTS ◄DEF XXXXX LO XXXXX HI XXXXX<br />

LOCAL CONTROL RANGE = +/- X.X °F<br />

Pressing the SETPOINTS key or the ▼ (ARROW) key<br />

a third time will display the remote setpoint and cooling<br />

range. This display automatically updates about<br />

112<br />

SETPOINTS KEY<br />

SETPOINTS<br />

KEY<br />

LD10605<br />

FORM 201.28-NM1.1<br />

ISSUE DATE: 8/29/2012<br />

every 2 seconds. This remote setpoint message is show<br />

below:<br />

SETPOINTS REMOTE SETPOINT = XXX.X °F<br />

REMOTE CONTROL RANGE = +/- X.X °F<br />

If there is no remote setpoint being utilized, the remote<br />

setpoint value will be displayed as XXXXXX and the<br />

remote Control Range will display XXX.<br />

Pressing the SETPOINTS key or the Arrow key a<br />

fourth time will bring up a screen that allows the Maximum<br />

Remote Temperature Reset to be programmed.<br />

This message is show below:<br />

SETPOINTS ◄DEF XXXXX LO XXXXX HI XXXXX<br />

MAXIMUM REMOTE TEMP RESET = XXX.X °F<br />

The values displayed under each of the key presses<br />

may be changed by keying in new values and pressing<br />

the � (ENTER) key to store the new value into memory.<br />

Where more than one value may be keyed in on a<br />

display, a portion of the data that does not need updating<br />

may be skipped by pressing the � (ENTER) key.<br />

The � (ENTER) key must also be pressed after the<br />

last value in the display to store the data into memory.<br />