SECTION 8 - MICROPANEL<br />

Display Units Mode<br />

OPTIONS DISPLAY UNITS<br />

◄ ► XXXXXXXXXXXXXXXXXXXX<br />

This message indicates whether SI (°C, barg) or Imperial<br />

units (°F, PSIG) was selected at the time of the<br />

fault.<br />

System Lead/Lag Control Mode<br />

OPTIONS LEAD / LAG CONTROL MODE<br />

◄ ► XXXXXXXXXXXXXXXXXXXXX<br />

This message indicates the type of lead lag control selected<br />

at the time of the fault. Three choices are available:<br />

110<br />

• Automatic<br />

• Sys 1 Lead<br />

• Sys 2 Lead<br />

The default mode will be AUTOMATIC.<br />

Remote Temperature Reset<br />

OPTIONS REMOTE TEMP RESET INPUT<br />

◄ ► XXXXXXXX<br />

This message indicates whether temperature reset was<br />

active or disabled at the chiller keypad at the time of<br />

the fault and if active, the type of reset signal selected.<br />

If the option is not factory enabled, the option will not<br />

appear.<br />

Remote Current Reset<br />

OPTIONS REMOTE CURRENT LIMIT INPUT<br />

◄ ► XXXXXXXXXXX<br />

This message indicates whether remote current reset<br />

was active or disabled at the chiller keypad at the time<br />

of the fault and if active, the type of reset signal selected.<br />

If the option is not factory enabled, the option will not<br />

appear.<br />

Remote Sound Limit Selection<br />

OPTIONS REMOTE SOUND LIMIT INPUT<br />

◄ ► XXXXXXXXXXX<br />

This message indicates whether remote sound limit<br />

was active or disabled at the chiller keypad at the time<br />

of the fault and if active, the type of reset signal selected.<br />

FORM 201.28-NM1.1<br />

ISSUE DATE: 8/29/2012<br />

If the option is not factory enabled, the option will not<br />

appear.<br />

Program Values<br />

Suction Pressure Cutout<br />

PROGRAM<br />

SUCTION PRESSURE CUTOUT = XXX.X PSIG<br />

This message indicates the he suction pressure cutout<br />

programmed at the time of the fault.<br />

Low Ambient Cutout<br />

PROGRAM<br />

LOW AMBIENT TEMP CUTOUT = XXX.X °F<br />

This message displays the low ambient temp cutout<br />

programmed at the time of the fault.<br />

Low Leaving Chilled <strong>Liquid</strong> Temp Cutout<br />

PROGRAM<br />

LEAVING LIQUID TEMP CUTOUT = XXX.X °F<br />

This message displays the low leaving chilled liquid<br />

temperature cutout programmed at the time of the fault.<br />

Motor Current Limit<br />

PROGRAM<br />

MOTOR CURRENT LIMIT = XXX %FLA<br />

This message indicates the motor current limit programmed<br />

at the time of the fault.<br />

Pulldown Current Limit<br />

PROGRAM<br />

PULLDOWN CURRENT LIMIT = XXX %FLA<br />

This message indicates the pulldown current limit programmed<br />

at the time of the fault.<br />

Pulldown Current Limit Time<br />

PROGRAM<br />

PULLDOWN CURRENT LIMIT TIME = XXX MIN<br />

This message indicates the pulldown current limit time<br />

programmed at the time of the fault.<br />

Condenser Subcooling Setpoint<br />

PROGRAM<br />

SUBCOOLING SETPOINT = XXX.X °F<br />

This message indicates the liquid subcooling setpoint<br />

programmed at the time of the fault.<br />