FORM 201.28-NM1.1<br />

ISSUE DATE: 8/29/2012<br />

Condenser Fans<br />

SYS 1 CONDENSER FANS ON = X<br />

SYS 1 CONDENSER FANS ON = X<br />

VSD FAN SPEED XX.X V = XXX %<br />

This message displays the number of condenser fans<br />

ON or the optional VSD fan control speed signal to the<br />

inverter and the % of full speed.<br />

VI Step Solenoid<br />

SYS 1 VI STEP SOLENOID 1 = XXX<br />

VI STEP SOLENOID 2 = XXX<br />

This message displays whether the VI solenoids were<br />

ON or OFF at the time of the fault.<br />

Compressor #1 Run Time<br />

SYS 1 RUN TIME<br />

XX DAYS XX HOURS XX MINUTES XX SECONDS<br />

This message displays the system run time since the<br />

last start in days, hours, minutes, and seconds at the<br />

time of the fault.<br />

System #1 Run Signals<br />

SYS 1 RUN SIGNALS RELAY = XXX<br />

RUN PERM = XXX SOFTWARE = XXX<br />

This message displays the System Run Signal Relay<br />

(Relay Output Board) status, Run Permissive Input<br />

status, and the Internal Software (microprocessor command)<br />

ON/OFF Start status. The status of each will indicate<br />

either ON or OFF.<br />

System 2 Data<br />

Data for the system 2 at the time of the fault is displayed<br />

in the same sequence as the system #1 data.<br />

Compressor Operating Hours and Starts<br />

HOURS 1=XXXXX, 2=XXXXX<br />

START 1=XXXXX, 2=XXXXX<br />

This message displays compressor operating hours and<br />

compressor starts at the time of the fault.<br />

Chilled <strong>Liquid</strong> Setpoint Cooling Setpoints<br />

SETPOINTS<br />

LOCAL COOLING SETPOINT = XXX.X °F<br />

This message displays the programmed cooling<br />

setpoint at the time of the fault.<br />

SECTION 8 - MICROPANEL<br />

SETPOINTS<br />

LOCAL CONTROL RANGE = +/- X.X °F<br />

This message displays the programmed Control Range<br />

at the time of the fault.<br />

Remote Setpoint and Range<br />

SETPOINTS REMOTE SETPOINT = XXX.X °F<br />

REMOTE CONTROL RANGE = +/- X.X °F<br />

This message displays the remote setpoint and Control<br />

Range at the time of the fault.<br />

Maximum Remote Temperature Setpoint<br />

SETPOINTS<br />

MAXIMUM REMOTE TEMP RESET = XXX.X °F<br />

This message displays the maximum remote reset programmed<br />

at the time of the fault.<br />

Options<br />

Display Language<br />

OPTIONS DISPLAY LANGUAGE<br />

◄ ► XXXXXXXXXXXXXXXXXXXX<br />

This message displays the language selected at the time<br />

of the fault.<br />

Chilled <strong>Liquid</strong> Cooling Mode<br />

OPTIONS CHILLED LIQUID COOLING MODE<br />

◄ ► WATER COOLING<br />

This message displays the chilled liquid temperature<br />

mode (water or glycol) selected at the time of the fault.<br />

Local / Remote Control Mode<br />

OPTIONS CHILLED LIQUID COOLING MODE<br />

◄ ► GLYCOL COOLING<br />

This message indicates whether Local or Remote Control<br />

Mode was selected at the time of the fault.<br />

OPTIONS LOCAL / REMOTE CONTROL MODE<br />

◄ ► XXXXXXXXXXXXXXXXXXXXX<br />

When Remote Control Mode is selected, control of the<br />

Chilled <strong>Liquid</strong> Setpoint is from a remote device such<br />

as an ISN/BAS controller.<br />

JOHNSON CONTROLS 109<br />