SECTION 8 - MICROPANEL<br />

IGBT Baseplate Temperature<br />

VSD IGBT BASEPLATE TEMPS T1 = XXX °F<br />

T2 = XXX °F<br />

This message displays the IGBT highest baseplate<br />

temperature for 2 and 3 compressor units at the time of<br />

the fault. 4 compressor units display temperatures for<br />

1/3 (T1) and 2/4 (T2).<br />

Precharge Signal Status and VSD Cooling<br />

Status<br />

VSD PRECHARGE SIGNAL = XXX<br />

This display provides the state of the precharge signal,<br />

where XXX is either ON or OFF at the time of the<br />

fault.<br />

Compressor #1 and #2, 105% FLA Motor<br />

Overload Current Setting<br />

VSD COMP 1 MOTOR OVERLOAD = XXX AMPS<br />

COMP 2 MOTOR OVERLOAD = XXX AMPS<br />

This message displays the setting of the VSD’s 100%<br />

FLA potentiometer for Compressor #1 and #2 at the<br />

time of the fault.<br />

System Data<br />

System #1 Pressures<br />

SYS 1 PRESSURES OIL = XXXX PSIG<br />

DISCHARGE = XXXX PSIG<br />

This message displays the measured system oil and<br />

discharge pressures at the time of the fault.<br />

SYS 1 PRESSURES SUCTION = XXXX PSIG<br />

CONDENSER LIQUID = XXXX PSIG<br />

This message displays the measured system suction<br />

and condenser liquid line pressure at the time of the<br />

fault.<br />

System # 1 Temperatures<br />

SYS 1 TEMPERATURES OIL = XXX.X °F<br />

EDUCTOR = XXX.X °F<br />

This message displays the measured system oil and<br />

eductor temperatures at the time of the fault.<br />

108<br />

FORM 201.28-NM1.1<br />

ISSUE DATE: 8/29/2012<br />

SYS 1 CONDENSER LIQUID TEMP = XXX.X °F<br />

SUBCOOLING = XXX.X SAT TEMP = XXX.X °F<br />

This message displays the condenser liquid, liquid line<br />

subcooling and saturated discharge temperatures at the<br />

time of the fault.<br />

SYS 1 DISCHARGE TEMP = XXX.X °F<br />

SUPERHEAT = XXX.X SAT TEMP = XXX.X °F<br />

This message displays the system discharge, discharge<br />

superheat and saturated discharge temperatures at the<br />

time of the fault.<br />

Compressor Speed and Heater Status<br />

SYS 1 COMPRESSOR SPEED = XXX.X %<br />

HEATER = XXX.X °F<br />

This message indicates the compressor speed in % and<br />

the heater status at the time of the fault.<br />

System #1 Motor Temperatures<br />

SYS 1 MOTOR TEMPS T1 = XXX.X °F<br />

T2 = XXX.X T3 = XXX.X °F<br />

This message displays the System 1 motor thermistor<br />

temperatures at the time of the fault.<br />

Flash Tank Level and Economizer Position<br />

SYS 1 FLASH TANK LEVEL Y 512 ADC<br />

ECONOMIZER VALVE = XXX.X %<br />

This message displays the flash tank level and the<br />

economizer valve position in % at the time of the fault.<br />

Condenser Subcooling and Condenser Drain<br />

Valve Position<br />

SYS 1 CONDENSER SUBCOOLING = XXX.X °F<br />

CONDENSER DRAIN VALVE = XXX.X %<br />

This message displays the condenser subcooling and<br />

the Condenser Drain Valve position at the time of the<br />

fault.<br />