FORM 201.28-NM1.1<br />

ISSUE DATE: 8/29/2012<br />

Ambient <strong>Air</strong> Temperature<br />

UNIT<br />

OUTSIDE AMBIENT AIR TEMP = XXX.X °F<br />

This message indicates the ambient air temperature at<br />

the time of the fault.<br />

Load / Unload Timers<br />

UNIT LOAD TIMER = XXX SEC<br />

UNLOAD TIMER = XXX SEC<br />

This message indicates remaining time on the load and<br />

unload timers at the time of the fault.<br />

Chilled <strong>Liquid</strong> Temperature Error and Rate of<br />

Change<br />

UNIT TEMP ERROR = XXX.X °F<br />

RATE = XXX.X °F/M<br />

This message indicates the temperature error between<br />

the actual and the programmed setpoint at the time of<br />

the fault and the rate of temperature change.<br />

Programmed Lead System Selection and<br />

Flow Switch Status<br />

UNIT LEAD SYSTEM NUMBER = X<br />

FLOW SWITCH = XXX<br />

This message indicates the designated lead system at<br />

the time of the fault and whether the flow switch was<br />

ON (Closed) or OFF (Open) at the time of the fault.<br />

Evaporator Pump and Evaporator Heater<br />

Status<br />

UNIT EVAP PUMP RUN = XXX<br />

EVAP HEATER = XXX<br />

This message indicates the status of the evaporator<br />

pump and the evaporator heater at the time of the fault.<br />

XXX indicates ON or OFF.<br />

Active Remote Control Status<br />

UNIT ACTIVE REMOTE CONTR0L = XXXXXX<br />

This message indicates whether the system was operating<br />

under Active Remote Control (RCC, ISN, LOAD,<br />

TEMP, or SOUND) or standard control (NONE) at the<br />

time of the fault.<br />

SECTION 8 - MICROPANEL<br />

UNIT SOUND LIMIT LOCAL = XXX %<br />

ISN = XXX REMOTE = XXX %<br />

This message indicates that sound limiting was in effect,<br />

the amount, and whether it was local or remotely<br />

limited.<br />

VSD Data<br />

VSD Actual and Command Frequency<br />

VSD FREQUENCY ACTUAL = XXX.X HZ<br />

COMMAND = XXX.X HZ<br />

This message indicates the VSD actual operating frequency<br />

and the command frequency at the time of the<br />

fault. Actual and command may not match due to load/<br />

unload timers, limitation of 1 Hz per load/unload increment,<br />

and to allowable acceleration/deceleration of the<br />

motor.<br />

Compressor Amps and %FLA<br />

The message indicates the compressor %FLA and motor<br />

currents for systems 1 and 2 at the time of the fault.<br />

COMP 1 = XXX AMPS = XXX %FLA<br />

COMP 2 = XXX AMPS = XXX %FLA<br />

VSD Current Limit<br />

VSD CURRENT LIMIT LOCAL = XXX %FLA<br />

ISN = XXX REMOTE = XXX %FLA<br />

This message displays the current limit values as set<br />

locally, by an ISN, or a remote current limiting input at<br />

the time of the fault.<br />

DC BUS Voltage<br />

VSD DC BUS VOLTAGE = XXX VDC<br />

This message displays the DC Bus voltage at the time<br />

of the fault.<br />

VSD Internal Ambient Temp<br />

VSD INTERNAL AMBIENT TEMP = XXX.X °F<br />

COOLING SYSTEM STATUS = YYY<br />

This message displays the VSD/Microprocessor internal<br />

ambient cabinet temperature and the cooling system<br />

status (ON or OFF) at the time of the fault.<br />

JOHNSON CONTROLS 107<br />