FORM 201.28-NM1.1<br />
ISSUE DATE: 8/29/2012<br />
Ambient <strong>Air</strong> Temperature<br />
UNIT<br />
OUTSIDE AMBIENT AIR TEMP = XXX.X °F<br />
This message indicates the ambient air temperature at<br />
the time of the fault.<br />
Load / Unload Timers<br />
UNIT LOAD TIMER = XXX SEC<br />
UNLOAD TIMER = XXX SEC<br />
This message indicates remaining time on the load and<br />
unload timers at the time of the fault.<br />
Chilled <strong>Liquid</strong> Temperature Error and Rate of<br />
Change<br />
UNIT TEMP ERROR = XXX.X °F<br />
RATE = XXX.X °F/M<br />
This message indicates the temperature error between<br />
the actual and the programmed setpoint at the time of<br />
the fault and the rate of temperature change.<br />
Programmed Lead System Selection and<br />
Flow Switch Status<br />
UNIT LEAD SYSTEM NUMBER = X<br />
FLOW SWITCH = XXX<br />
This message indicates the designated lead system at<br />
the time of the fault and whether the flow switch was<br />
ON (Closed) or OFF (Open) at the time of the fault.<br />
Evaporator Pump and Evaporator Heater<br />
Status<br />
UNIT EVAP PUMP RUN = XXX<br />
EVAP HEATER = XXX<br />
This message indicates the status of the evaporator<br />
pump and the evaporator heater at the time of the fault.<br />
XXX indicates ON or OFF.<br />
Active Remote Control Status<br />
UNIT ACTIVE REMOTE CONTR0L = XXXXXX<br />
This message indicates whether the system was operating<br />
under Active Remote Control (RCC, ISN, LOAD,<br />
TEMP, or SOUND) or standard control (NONE) at the<br />
time of the fault.<br />
SECTION 8 - MICROPANEL<br />
UNIT SOUND LIMIT LOCAL = XXX %<br />
ISN = XXX REMOTE = XXX %<br />
This message indicates that sound limiting was in effect,<br />
the amount, and whether it was local or remotely<br />
limited.<br />
VSD Data<br />
VSD Actual and Command Frequency<br />
VSD FREQUENCY ACTUAL = XXX.X HZ<br />
COMMAND = XXX.X HZ<br />
This message indicates the VSD actual operating frequency<br />
and the command frequency at the time of the<br />
fault. Actual and command may not match due to load/<br />
unload timers, limitation of 1 Hz per load/unload increment,<br />
and to allowable acceleration/deceleration of the<br />
motor.<br />
Compressor Amps and %FLA<br />
The message indicates the compressor %FLA and motor<br />
currents for systems 1 and 2 at the time of the fault.<br />
COMP 1 = XXX AMPS = XXX %FLA<br />
COMP 2 = XXX AMPS = XXX %FLA<br />
VSD Current Limit<br />
VSD CURRENT LIMIT LOCAL = XXX %FLA<br />
ISN = XXX REMOTE = XXX %FLA<br />
This message displays the current limit values as set<br />
locally, by an ISN, or a remote current limiting input at<br />
the time of the fault.<br />
DC BUS Voltage<br />
VSD DC BUS VOLTAGE = XXX VDC<br />
This message displays the DC Bus voltage at the time<br />
of the fault.<br />
VSD Internal Ambient Temp<br />
VSD INTERNAL AMBIENT TEMP = XXX.X °F<br />
COOLING SYSTEM STATUS = YYY<br />
This message displays the VSD/Microprocessor internal<br />
ambient cabinet temperature and the cooling system<br />
status (ON or OFF) at the time of the fault.<br />
JOHNSON CONTROLS 107<br />
8