FORM 201.28-NM1.1<br />

ISSUE DATE: 8/29/2012<br />

HISTORY<br />

KEY<br />

History Key Operation<br />

The HISTORY key provides the user access to many<br />

unit and system operating parameters captured at the<br />

instant a unit or system safety (fault) shutdown occurs.<br />

The history buffer will also capture system data at the<br />

time of normal shutdowns such as cycling shutdowns.<br />

When the HISTORY key is pressed the following<br />

screen is displayed:<br />

HISTORY CHOOSE HISTORY TYPE<br />

◄ ► XXXXXXXXXXXXXXXXXXXXXXXXXXXX<br />

The ◄ and ► (ARROW) keys allow choosing between<br />

NORMAL SHUTDOWNS and FAULT SHUT-<br />

DOWNS. “Fault” shutdowns provide information on<br />

safety shutdowns, while “Normal” shutdowns provide<br />

chiller cycling information on temperature (demand),<br />

cycling, remote, system switch, etc., shutdowns that<br />

are non-safety related shutdowns. Once the selection<br />

is made, the � (ENTER) key must be pressed to enter<br />

the selection.<br />

Normal Shutdowns History<br />

If the NORMAL SHUTDOWNS History is selected,<br />

the following screen will be displayed:<br />

NORM HIST XX 18-JUN-20004 10:34:58 AM<br />

YYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYY<br />

HISTORY KEY<br />

SECTION 8 - MICROPANEL<br />

JOHNSON CONTROLS 105<br />

LD10605<br />

XX is the normal shutdown number. The display will<br />

provide date and time of the shutdown and the reason<br />

for the cycling shutdown (YYY….).<br />

The operator can view any of the stored 20 single display<br />

normal shutdown history buffers. History buffer<br />

number 1 provides the most recent shutdown information<br />

and buffer number 20 is the oldest safety shutdown<br />

information saved. The ◄ and ► (ARROW) keys allow<br />

scrolling between each of the history buffers. The ►<br />

(ARROW) key scrolls to the next normal history shutdown<br />

and the ◄ (ARROW) key scrolls to the previous<br />

normal history shutdown.<br />

The following display will typically be displayed on a<br />

normal shutdown due to shutdown on lack of cooling<br />

demand.<br />

NORM HIST XX 18-JUN-20004 10:34:58 AM<br />

SYS X COOLING DEMAND SHUTDOWN<br />

Fault Shutdowns History<br />

If the FAULT SHUTDOWNS History is selected, the<br />

following screen will be displayed:<br />

FAULT HIST XX 18-JUN-20004 10:34:58 AM<br />

YYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYY<br />