FORM 201.28-NM1.1<br />

ISSUE DATE: 8/29/2012<br />

General<br />

VSD<br />

DATA KEY<br />

The VSD DATA key provides the user with displays of<br />

VSD temperatures, voltages, currents, and other operating<br />

data. This key has multiple displays, which can<br />

be seen by repeatedly pressing the VSD DATA or the<br />

▲ or ▼ (Arrow) keys. An explanation of each message<br />

is provided below.<br />

VSD Data Key Operation<br />

The first VSD DATA key press displays the actual VSD<br />

Output Frequency and Command Frequency.<br />

VSD FREQUENCY ACTUAL = XXX.X HZ<br />

COMMAND = XXX.X HZ<br />

The second key press of the VSD DATA key or the ▼<br />

(ARROW) key displays the calculated compressor %<br />

FLA and measured motor currents in amps for systems<br />

1 and 2. When measuring motor current keep in mind<br />

that measuring inverter PWM current is difficult and<br />

meter error can be significant.<br />

VSD COMP 1 = XXX AMPS = XXX %FLA<br />

COMP 2 = XXX AMPS = XXX %FLA<br />

The next key press displays the current limit values<br />

set locally on the panel under the PROGRAM key, remotely<br />

by an ISN, and remotely by the Current Limit<br />

input. Any current limits that are inactive will display<br />

“XXX” instead of a numeric value.<br />

VSD CURRENT LIMIT LOCAL = XXX %FLA<br />

ISN = XXX REMOTE = XXX %FLA<br />

VSD DATA KEY<br />

SECTION 8 - MICROPANEL<br />

JOHNSON CONTROLS 103<br />

LD10605<br />

The next key press displays DC Bus voltage.<br />

VSD DC BUS VOLTAGE = XXX VDC<br />

The next key press displays the Control Panel/VSD Internal<br />

Ambient Temperature and VSD Cooling Pump/<br />

Fan Status. YYY will indicate ON or OFF.<br />

VSD INTERNAL AMBIENT TEMP = XXX.X °F<br />

COOLING SYSTEM STATUS = YYY<br />

The next key press displays the IGBT highest baseplate<br />

temperature.<br />

VSD IGBT BASEPLATE TEMPS T1 = XXX °F<br />

T2 = XXX °F<br />

The next key press displays the state of the Precharge<br />

signal, where XXX is either ON or OFF.<br />

VSD PRECHARGE SIGNAL = XXX<br />

The next key press displays the setting of the VSD’s<br />

105% FLA overload potentiometer for Compressor #1<br />

and 2. The settings are determined by the adjustment of<br />

the overload potentiometers on the VSD Logic Board.<br />

These pots are factory set and should not require changing<br />

unless the circuit board is replaced.<br />

VSD COMP 1 MOTOR OVERLOAD = XXX AMPS<br />

COMP 2 MOTOR OVERLOAD = XXX AMPS<br />

8