21.01.2013 Views

YVAA Style A Air-Cooled Screw Liquid Chillers ... - Johnson Controls

YVAA Style A Air-Cooled Screw Liquid Chillers ... - Johnson Controls

YVAA Style A Air-Cooled Screw Liquid Chillers ... - Johnson Controls

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

SECTION 8 - MICROPANEL<br />

Sensor Displays<br />

Table 9 lists all the sensors attached to the control<br />

board associated with system data keys. The minimum<br />

and maximum values displayed on the micro display<br />

are provided.<br />

TABLE 9 - SENSOR MIN/MAX OUTPUTS<br />

102<br />

SYSTEM SENSOR<br />

FORM 201.28-NM1.1<br />

ISSUE DATE: 8/29/2012<br />

SENSOR / INPUT TYPE MINIMUM VALUE MAXIMUM VALUE<br />

Suction Pressure Transducer 0.0 PSIG (0 barg) 125.0 PSIG (8.62 barg)<br />

Condenser <strong>Liquid</strong> Pressure Transducer 0.0 PSIG (0 barg) 400.0 PSIG (27.6 barg)<br />

Discharge Pressure Transducer 0.0 PSIG (0 barg) 400.0 PSIG (27.6 barg)<br />

Oil Pressure Transducer 0.0 PSIG (0 barg) 400.0 PSIG (27.6 barg)<br />

Flash Tank Level Switch Low High<br />

Condenser <strong>Liquid</strong> Temp Thermistor -4.1 °F (-20.06 °C) 155.6 °F (68.67°C)<br />

Leaving Chilled <strong>Liquid</strong> Temp Thermistor -19.1 °F (-28.49°C) 110.2 °F (43.44°C)<br />

Return Chilled <strong>Liquid</strong> Temp Thermistor -19.1 °F (-28.49°C) 110.2° F (43.44°C)<br />

Eductor Temp Thermistor -4.1° F (-20.06°C) 132.8 °F (56.00°C)<br />

Ambient <strong>Air</strong> Temp Thermistor -4.6 °F (-20.33°C) 137.9° F (58.83°C)<br />

Compressor Motor Temp Thermistor -30.2 °F (-34.56°C) 302.0° F (150.00°C)<br />

Discharge Temp Thermistor 40.3 °F (4.61°C) 302.6 °F (150.33°C)<br />

Remote Temp Reset<br />

Remote Current Limit<br />

Remote Sound Limit<br />

4 to 20ma, 0 to 10VDC,<br />

0 to 20ma or 2 to 10VDC<br />

4 to 20ma, 0 to 10VDC,<br />

0 to 20ma or 2 to 10VDC<br />

4 to 20ma, 0 to 10VDC,<br />

0 to 20ma or 2 to 10VDC<br />

If values exceed the limits in the table, a < (less than)<br />

or > (more than) sign will be display along with the<br />

minimum or maximum value.<br />

0% 100%<br />

0% 100%<br />

0% 100%<br />

JOHNSON CONTROLS