SECTION 8 - MICROPANEL<br />

General<br />

100<br />

SYSTEM 1<br />

DATA KEY<br />

SYSTEM 2<br />

DATA KEY<br />

SYSTEM 3<br />

DATA KEY<br />

SYSTEM 4<br />

DATA KEY<br />

The data keys provide the user with many displays of<br />

individual system temperatures, pressures, and other<br />

operating data. These keys have multiple displays,<br />

which can be seen by repeatedly pressing the SYSTEM<br />

DATA or the ▲ or ▼ (Arrow) keys. An explanation of<br />

each key and its messages is provided below.<br />

System 1 Data Key Operation<br />

The SYSTEM 1 DATA key provides the user with access<br />

to System 1 operating parameters. The following<br />

is a list of the data in the order in which it appears.<br />

The first key press of the SYSTEM X DATA key displays<br />

all of the measured system pressures (oil and discharge).<br />

SYS 1 PRESSURES OIL = XXXX PSIG<br />

DISCHARGE = XXXX PSIG<br />

The second key press of the SYSTEM DATA key or<br />

the ▼ (DOWN ARROW) key displays system suction<br />

and condenser liquid pressure.<br />

SYS 1 PRESSURES SUCTION = XXXX PSIG<br />

CONDENSER LIQUID = XXXX PSIG<br />

SYSTEM DATA KEYS 1 THROUGH 4<br />

FORM 201.28-NM1.1<br />

ISSUE DATE: 8/29/2012<br />

LD10605<br />

The next key press displays system oil and eductor<br />

temperatures.<br />

SYS 1 TEMPERATURES OIL = XXX.X °F<br />

EDUCTOR = XXX.X °F<br />

The next key press displays system condenser liquid<br />

temperature, liquid line subcooling and saturated discharge<br />

temperature on the liquid line.<br />

SYS 1 CONDENSER LIQUID TEMP = XXX.X °F<br />

SUBCOOLING = XXX.X SAT TEMP = XXX.X °F<br />

The next key press displays discharge temperature,<br />

discharge superheat and saturated discharge pressure<br />

at the compressor.<br />

SYS 1 DISCHARGE TEMP = XXX.X °F<br />

SUPERHEAT = XXX.X SAT TEMP = XXX.X °F<br />

The next key press displays the System 1 motor thermistor<br />

temperatures.<br />

SYS 1 MOTOR TEMPS T1 = XXX.X °F<br />

T2 = XXX.X °F T3 = XXX.X °F<br />

If any motor temp sensor is being ignored,<br />

(selectable under Unit Set-up Mode), that<br />

sensor’s value will be displayed as<br />

XXXXX.<br />