Additional Functions SMA Solar Technology AG<br />

12.7 Time-Controlled Standby<br />

You can set the <strong>Sun</strong>ny Island to standby mode in a time-controlled way. Activate the time-controlled<br />

standby using the parameter "250.13 SlpAtNgt". Set the parameter to "Enable".<br />

After activation, set the start time and the stop time for standby. Carry out the setting using the<br />

"250.14 SlpStrTm" and "250.15 SlpStpTm" parameters.<br />

12.8 Reaction in Case of Failures<br />

You can influence how the <strong>Sun</strong>ny Island reacts to failures occurring in a three-phase system using the<br />

"250.30 RnMod" parameter. The parameter is set to "RunAlways" at the factory. This means that the<br />

<strong>Sun</strong>ny Island master ignores all faults at the slave devices.<br />

If you set the parameter to "StopAlways", the system will be put in standby mode upon detection of a<br />

fault at the slave devices. Faults which can be removed via an autostart are not included.<br />

96 SI<strong>5048</strong>-TB-TEN110340 <strong>Technical</strong> <strong>Description</strong>