SMA Solar Technology AG Switching On and Off<br />

1. Switch the <strong>Sun</strong>ny Island DC circuit breaker to the "OFF" position.<br />

DANGER!<br />

Danger to life due to high voltages in the <strong>Sun</strong>ny Island.<br />

After an automatic disconnection, high residual voltages can remain in the <strong>Sun</strong>ny Island<br />

capacitors.<br />

• Wait at least 15 minutes to let the capacitors discharge and to allow the voltage<br />

inside the device to drop to a safe level.<br />

2. Switch the <strong>Sun</strong>ny Island DC circuit breaker to the "ON" position.<br />

☑ The display light of the <strong>Sun</strong>ny Island switches on.<br />

Switching on the DC circuit breaker<br />

If, in rare cases, the device cannot be switched back on after 15 minutes, wait a little longer<br />

and try it again.<br />

3. Switch on the <strong>Sun</strong>ny Island as described in section 9.1 ”Switching On” (page 62).<br />

Charging the batteries<br />

After reactivation, it is important that the batteries are charged. If an autostart generator is<br />

present in the stand-alone grid, the <strong>Sun</strong>ny Island will request the generator after a few<br />

minutes.<br />

4. Monitor the generator startup and check that the <strong>Sun</strong>ny Island switches to charge mode.<br />

5. Check for error-free functioning of all other energy generators in the system.<br />

Battery Preservation Mode after Reactivation<br />

If, after reactivation, the <strong>Sun</strong>ny Island immediately switches into battery preservation mode<br />

(see section 13.5 ”Battery Preservation Mode” (page 104)), disconnect all consumers<br />

from the AC output (AC1 and AC2).<br />

The consumers can be reconnected once the <strong>Sun</strong>ny Island enters the charge state.<br />

A precondition for this is that a generator capable of providing the required power is<br />

connected.<br />

For more information, see section 20.10 ”What to Do during Emergency Charge Mode”<br />

(page 213).<br />

<strong>Technical</strong> <strong>Description</strong> SI<strong>5048</strong>-TB-TEN110340 65