Initial Start-up SMA Solar Technology AG<br />

8.3 Commissioning the Battery Current Sensor<br />

In the event you have installed a battery current sensor in your system, you are required to synchronize<br />

the device's internal offset. To do this, proceed as follows:<br />

1. Switch the <strong>Sun</strong>ny Island to standby as described in section 9.2 ”Stopping the <strong>Sun</strong>ny Island<br />

(Standby)” (page 63).<br />

NOTICE!<br />

System error due to wrong parameters being entered.<br />

All parameter settings which could affect the operating safety of the stand-alone system are<br />

protected by the installer password.<br />

• Only electrically skilled persons are permitted to set and adjust system parameters.<br />

• Enter the password as described in section 10.5 ”Entering the Installer Password”<br />

(page 76).<br />

2. Short-circuit the battery current sensor cables.<br />

– BatCur+ to terminal 1<br />

– BatCur − to terminal 1<br />

3. Set the following parameters:<br />

Choose the type of battery current sensor:<br />

– "225.01 BatCurSnsTyp" (None / 50 mV / 60 mV). Only after activation of the parameter<br />

with 50 mV or 60 mV other parameters (02, 03 and 04 in the menu "225# Battery Current<br />

Sensor") will be shown and activated.<br />

4. Set the nominal current for the battery current sensor (e.g., 400 A / 60 mV):<br />

– "225.02 BatCurGain60" (for a 60 mV output)<br />

– "225.03 BatCurGain50" (for a 50 mV output)<br />

5. Start automatic calibration:<br />

– Set "225.04 BatCurAutoCal" to "Start".<br />

☑ The <strong>Sun</strong>ny Island conducts an automatic calibration.<br />

6. Check the offset error:<br />

Display value "120.06 TotBatCur" should be (close to) zero.<br />