Electrical Connection SMA Solar Technology AG<br />
Generator start<br />
The <strong>Sun</strong>ny Island can control generators. The <strong>Sun</strong>ny Island directly supports generators that can be<br />
started and stopped using a single contact. Generators which require more than one contact must be<br />
connected to the <strong>Sun</strong>ny Island via a Generator Manager (GenMan). This product can be acquired<br />
from SMA Solar Technology.<br />
Default setting of the relays<br />
Relay 1 is preset to the "AutoGn" generator start function and relay 2 to the "AutoLodSoc"<br />
load shedding function.<br />
6.4.5 BatVtgOut Power Supply<br />
The battery voltage is conducted to the outside at these terminals. The battery voltage is fused at both<br />
poles by PTC resistors (max. 0.6 A). Depending on the internal temperature of the <strong>Sun</strong>ny Island, the<br />
tripping threshold is higher than 0.6 A.<br />
This connection can be used, for example, to supply a DC contactor for load shedding.<br />
For connection, proceed as follows:<br />
1. Pierce a hole in the rubber connection area at the corresponding position.<br />
2. Starting from the outside, lead the insulated conductors with bootlace ferrules through the hole<br />
in the <strong>Sun</strong>ny Island.<br />
3. Connect the wires correspondingly to the "BatVtgOut" terminal of the 4-pole print terminal<br />
included in the delivery.<br />
4. Tighten the terminals.<br />
5. Insert the 4-pole print terminal into the "BatVtgOut" socket on the <strong>Sun</strong>ny Island.<br />
48 SI<strong>5048</strong>-TB-TEN110340 <strong>Technical</strong> <strong>Description</strong>